Characteristics (continued)
0
Contactors and Starters 0
Type S, NEMA-style
Contactors and starters
Characteristics (continued)
Pole characteristics
Class 8502, 8536, 8702, 8736
Size 00 0 1 2 3 4 5 6 7
Number of poles 3-pole devices
3
Rated operational voltage Up to
V 600
Frequency limits Of the operational current
Hz 50/60
Conventional rated thermal current
A 9 18 27 45 90 135 270 540 810
Rated making capacity At 600 V
10 x rated current
Rated breaking capacity At 600 V
10 x rated current
Permissible short time
rating
Service limit current
A 11 21 32 52 104 156 311 621 932
a.c. control circuit characteristics
Class 8502, 8536, 8702, 8736
Size 00 0 1 2 3 4 5 6 7
Rated control circuit voltage
V 600
Average consumption 50 Hz Inrush
VA N/A 232 232 296 676 1260 1300 1495 (1)
Sealed
VA N/A 26 26 36 47 89 14 56 (1)
Average consumption 60 Hz Inrush
VA 165 245 245 311 700 1185 1300 1780 (1) 1960 (1)
Sealed
VA 33 27 27 37 46 85 14 48 (1) 59 (1)
Heat dissipation 50/60Hz 50 Hz
W N/A 7.7 7.7 12 15 23.4 13 27
60 Hz
W 6 7.8 7.8 14 14 22 13 32 36
Operating time (2) Closing "C"
ms 9.1 - 23.2 8.4 - 20.1 8.4 - 20.1 14.6 - 27.6 17.3 - 32.3 13.0- 43.9 40 - 60 57.0- 74.0 43.8
Opening "O"
ms 5.29 - 15.9 2.4 - 15.9 2.4 - 15.9 16.3 - 22.8 9.6 - 18.7 11.2 -21.7 50 - 75 28.3 - 31.8 54.3
Mechanical life In millions of op. cycles
6 10 10 10 5 3 2 1.5 0.5
Maximum operating rate (3) In op. cycles per hour
9000 9000 9000 5400 4500 4500 180 180 180
Power circuit connections (connection via lug)
Type of lug Screw clamp terminal Box lug Parallel groove
Wire sizes (Min./max.) Solid or stranded copper
wire (AWG)
#14–#8 #14–#8 #14–#8 #14–#4 #14–
#1/0
#8–
250kcmil
#4–
500kcmil
1 or 2,
250–
500kcmil
per phase
1 to 4,
250–
500kcmil
per phase
Control circuit connections (connection via lug)
Type of lug Screw clamp terminal
Wire sizes (Min./max.) Solid or stranded copper
wire (AWG)
#16–#12
(1) Size 6 and 7 have a d.c. coil. The values shown are for the a.c. input to the d.c. power supply that provides power to the coil.
(2) The closing time "C" is measured from the moment that the coil supply is switched on to the initial contact of the main poles. The opening time "O" is measured
from the moment that the coil supply is switched off to the moment that the main poles separate.
(3) Operating cycles are without a load (mechanical life).
References:
pages 1/6 to 1/13
Dimensions:
pages 1/14 to 1/17