Brochure

6/3
6
Characteristics
0
Manual Starters and Switches 0
Manual starters Class 2510
Manual switches Class 2510
Reversing drum switches Class 2601
Environment
Class 2510/2601
Type F/K/T/M
Conforming to standards Enclosed unit
UL
Open unit
UL
Product certifications
CSA
Ambient air temperature around the
device
Storage
°C 0…+ 40
Operation
°C 0…+ 40
Electrical characteristics
Class 2510
Type F
Voltage rating
V a 277 maximum (single- or 2-pole); c 230 maximum (2-pole only)
Continuous current rating
A 16
Maximum Horsepower
115–230 V a Single-phase Single-pole hp/kW 1/0.75
2-pole
hp/kW 1/0.75
c 2-pole only
hp/kW 0.75/0.55
277 V a Single-phase Single-pole
hp/kW 1/0.75
2-pole
hp/kW 1/0.75
c 2-pole only
hp/kW
Class 2510
Type Kpp1/Kpp3 Kpp2/Kpp4 Kpp5 Kpp6
Number of poles
2 3 2 3
Number of phases
Single phase Three phase Single phase Three phase
Voltage rating
V a 600 maximum; c 230 maximum
Continuous current rating
A 30 at 600 V maximum
Maximum motor power
a rating 115 V hp/kW 2/1.5 2/1.5 2/1.5 2/1.5
230 V
hp/kW 2/1.5 7.5/5.6 3/2.2 7.5/5.6
460 V
hp/kW 3/2.2 10/7.5 7.5/5.6 15/11.2
575 V
hp/kW 3/2.2 10/7.5 10/7.5 20/14.9
c rating 90 V
hp/kW 1/0.75 1/0.75 1/0.75 1/0.75
115 V
hp/kW 2/1.5 2/1.5 2/1.5 2/1.5
230 V
hp/kW 1.5/1.1 1.5/1.1 1.5/1.1 1.5/1.1
Class 2510
Type TBp p/MBp p TCp p/MCp p MCp 2
Size
Available in NEMA Sizes M-0, M-1 and M-1P
Number of poles
a : 2-pole single-phase; 3-pole 3-phase
c : 2-pole (without low voltage protection only)
Voltage rating
V a 600 maximum; c 250 maximum
Terminals
Power terminals Type of lug Screw clamp
terminal
Screw clamp
terminal
Box lug
Wire Size (min.-max.)
#14–#8 #14–#8 #14–#6
Auxiliary interlock terminals Type of lug
Screw clamp
terminal
Screw clamp
terminal
Screw clamp terminal
Wire Size (min.-max.)
#16–#12 #16–#12 #16–#12
Class 2601
Type AG2/AG2 S2/BG1/BG1 S4
Voltage rating
V a 600 maximum; c 250 maximum
References:
pages 6/4 to 6/9
Dimensions:
pages 6/10 and 6/11