Brochure
5/3
5
Characteristics (continued)
0
Lighting Contactors 0
Multipole lighting contactors
Types L, LX and S Class 8903
Electrical characteristics (continued)
Class 8903
Type Lp/LXp SMp SPp SQp SVp SXp SYp SZp SJp
Contactor continuous rating
A 30 30 60 100 200 300 400 600 (1) 800
a Voltage ratings
Tungsten lamp loads
Single-pole to load a V 20 A/277 277 –
2-pole to load on single-phase and 3-pole to load on
3-phase
a V 20 A/480 480 –
Ballast loads
Single-pole to load a V 277 (2) 347
2-pole to load on single-phase and 3-pole to load on
3-phase
a V 480 (2) 600
Resistive loads
a VSingle-pole to load 20 A/600 600
2-pole to load on single-phase and 3-pole to load on
3-phase
a V 20 A/600 600
c Voltage ratings
Tungsten lamp or resistance loads
2-pole in series c V 125 250 –
3-pole in series
c V 20 A/250 250
UL-listed short-circuit rating
Contactors protected by fused disconnect switches
Maximum Class RK5 fuse rating A 30 30 60 100 200 400 400 – –
Maximum voltage
V 600 480 600 – –
Available Amperes (RMS sym)
kA 100 – 30 (5)
Contactors protected by circuit breakers
Maximum circuit breaker rating A 25 40 80/90 125 250/225 400 800 800 1200
Recommended circuit breaker type
Thermal-magnetic
Maximum voltage
V 240/480 480/600/480 600/480 600
Available Amperes (RMS sym)
kA 22/14 10/5/100
18/14/100
10/100 14/100 22/100 22 30
Kilowatt ratings (3)
Voltage
kW 6.9 10.3 20.7 34.6 69.2 103.9 138.5 207.8 277.1a 200 V
a 230 V
kW 7.9 11.9 23.9 39.8 79.6 119.5 159.3 239 318.7
a 380 V
kW 13.1 19.7 39.4 65.8 131.6 197.4 263.2 394.9 526.5
a 460 V
kW 15.9 23.9 47.8 79.8 159.3 239 318.6 478 637.4
a 575 V
kW 19.9 30 60 99 199 299 398.4 597.6 796.7
Motor power ratings equivalent to NEMA Size contactor
– Size 1 Size 2 Size 3 Size 4 Size 5 Size 6 Size 6 Size 7
Mixed load ratings
Percent lighting (and/or resistive) load: 0%
Motor voltage and phases (4)
200 V / 3-phase Max. motor hp – 7.5 10 25 40 75 125 150 250
230 V / 3-phase Max. motor
hp – 7.5 15 30 50 100 150 200 300
380 V / 3-phase Max. motor
hp – 10 25 50 75 150 250 300 400
460…575 V / 3-phase Max. motor
hp – 10 25 50 100 200 300 400 600
115 V / single-phase Max. motor
hp – 2 3 7.5 – – – – –
230 V / single-phase Max. motor
hp – 3 7.5 15 – – – – –
Percent lighting (and/or resistive) load: 75%
200 V / 3-phase Max. non-motor A – 22.5 45 75 150 225 300 450 600
Max. motor
hp – 1.5 3 5 15 20 30 50 60
230 V / 3-phase Max. non-motor
A – 22.5 45 75 150 225 300 450 600
Max. motor
hp – 2 3 7.5 15 25 30 50 75
380 V / 3-phase Max. non-motor
A – 22.5 45 75 150 225 300 450 600
Max. motor
hp – 3 7.5 10 30 40 60 75 125
460…575 V / 3-phase Max. non-motor
A – 22.5 45 75 150 225 300 450 600
Max. motor
hp – 3 10 15 30 50 75 100 150
115 V / single-phase Max. non-motor
A – 22.5 45 75 – – – – –
Max. motor
hp – 0.33 0.75 2 – – – – –
230 V / single-phase Max. non-motor
A – 22.5 45 75 – – – – –
Max. motor
hp – 0.75 2 3 – – – – –
(1) 600 A devices are derated to 540 A for resistance heating loads when aluminium wire is used.
(2) Types L and LX contactors also have a ballast lamp rating of 15 A/
a
347 V when connected single-pole to load and a 600 V when connected 2-pole to load on
single-phase and 3-pole to load on 3-phase.
(3) Resistance heating only (3-phase system).
(4) Select lighting contactor on basis of rated motor voltage, whether non-motor load is connected line-to-line or line-to-neutral.
(5) 30 kA also applies for Class J and Class K5, time-delay, 600 A maximum fuses. Additionally, 30 kA ratings apply to Class T, 1200 A maximum and Class L,
1600 A maximum fuses.
References:
pages 5/4 to 5/9
Dimensions:
pages 5/10 and 5/11