Brochure
4/3
4
Characteristics
0
Definite Purpose Contactors 0
Types DP and DPA Class 8910
Characteristics
Class 8910
Type DP
11/12
DP
21/22
DP
31/32
DP
41/42
DPA
12/13/
14
DPA
22/23/
24
DPA
32/33/
34
DPA
42/43/
44
DPA
52/53
DPA
62/63
DPA
72/73
DPA
92/93
DPA
122/
123
Environment
Rated insulation voltage
Conforming to UL, CSA V 600
Rated impulse withstand voltage kV 5
Conforming to standards
NEMA ICS-1, ICS-2 Yes
UL 508 Yes
Product certifications
UL Yes
CSA Yes
e Yes
Ambient air temperature around the device - 30…
Storage
°C 0…65 + 65
Operation
°C 0…65 0…40
Operating position
Without derating Vertical
Pole characteristics
Number of poles (P) 1, 2 2, 3, 4 2, 3
Rated operational voltage
Up to V 600
Frequency limits
Of the operational current Hz 50/60
Conventional thermal current (FLA) A 20 25 30 40 20 25 30 40 50 60 70 90 120
Rated making capacity (LRA)
At 240 V A – 120 150 180 240 300 360 450 540 720
At 277 V
A 100 125 150 200 –
At 480 V
A 100 125 150 150/
200
100 125 150 200 250 300 375 450 600
At 600 V
A 80 100 120 150/
160
80 100 120 160 200 240 300 360 480
Resistive rating
At 600 V A 30/30 30/35 40/40 50/50 25 35 40 50 62 75 94 120
a.c. control circuit characteristics
Rated control circuit voltage V 600 24/
600
Average consumption 60Hz
Inrush VA 30 56 (1) 109 214 700
Sealed
VA 6 6 (1) 10 19 46
Heat dissipation 60 Hz
Sealed W 2.5 2.7 (2) 3.3 7.5 14
Mechanical durability (3)
In thousands of operating cycles 500
Power circuit connections
Type of termination Binding head
screw
Screw
clamp
terminal
Box
lug
Binding head screw Box lug
Wire sizes (Min./max.) (4)
#14-#8 #14 -
#6
#14 - #8 #14-
#6
#14-#2 #14 - #1/0
Control circuit connections
Type of termination .250" Quick connect .250" Quick connect/binding head screw Screw
clamp
terminal
Wire sizes (Min./max.) (4) #16-#12
(1) 4-pole has 109 VA inrush, 10 VA sealed.
(2) 4-pole Watts are 3.3.
(3) Operating cycles are without a load (mechanical durability).
(4) Solid or stranded copper wire (AWG).
External auxiliary contacts
Type 9999 D10/D01/D11/D20/SX6/SX7/SX8/SX9/SX10
Voltage
a V 120 or less
Making current
a A 60 (35% power factor)
Breaking current
a A 6 (35% power factor)
Continuous current
A 10
General:
page 4/2
References:
pages 4/4 to 4/7
Dimensions:
pages 4/8 and 4/9