Brochure
1/8
1
References
0
Contactors and Starters 0
Type S, NEMA-style
Starters Class 8536
3-pole starters
NEMA
Size
Standard power ratings of 3-phase
motors 50/60 Hz
Motor volts
Contin-
uous
current
ratings
Enclosure
type (1)
Basic reference
Add code indicating
control circuit voltage
(2) and optional
variants (3) and “H”
code (4)
Weight
200 V 230 V 460 V 575 V
hp kW hp kW hp kW hp kW A kg (lb)
00 1.5 1.1 1.5 1.1 2 1.5 2 1.5 9 Open 8536 SAO 12 (2) (3) (4) 2 (4)
NEMA 1 8536 SAG 12 (2) (3) (4) 3 (8)
NEMA 12 8536 SBA 2 (2) (3) (4) 7 (16)
0 3 2.2 3 2.2 5 3.7 5 3.7 18 Open 8536 SBO 2 (2) (3) (4) 2 (4)
NEMA 1 8536 SBG 2 (2) (3) (4) 4 (8)
NEMA 12 8536 SBA 2 (2) (3) (4) 7 (16)
1 7.5 5.5 7.5 5.5 10 7.5 10 7.5 27 Open 8536 SCO 3 (2) (3) (4) 2 (4)
NEMA 1 8536 SCG 3 (2) (3) (4) 3 (8)
NEMA 12 8536 SCA 3 (2) (3) (4) 7 (16)
2 10 7.5 15 11 25 18.5 25 18.5 45 Open 8536 SDO 1 (2) (3) (4) 3 (6.75)
NEMA 1 8536 SDG 1 (2) (3) (4) 7 15.5)
NEMA 12 8536 SDA 1 (2) (3) (4) 10 (23)
3 25 18.5 30 22 50 37 50 37 90 Open 8536 SEO 1 (2) (3) (4) 6 (14)
NEMA 1 8536 SEG 1 (2) (3) (4) 17 (37)
NEMA 12 8536 SEA 1 (2) (3) (4) 31 (68)
4 40 30 50 37 100 75 100 75 135 Open 8536 SFO 1 (2) (3) (4) 8 (18)
NEMA 1 8536 SFG 1 (2) (3) (4) 25 (56)
NEMA 12 8536 SFA 1 (2) (3) (4) 33 (73)
5 75 55 100 75 200 150 200 150 270 Open 8536 SGO 1 (2) (3) (4) 20 (45)
NEMA 1 8536 SGG 1 (2) (3) (4) 73 (160)
NEMA 12 8536 SGA 1 (2) (3) (4) 80 (177)
6 150 110 200 150 400 300 400 300 540 Open 8536 SHO 2 (2) (3) (4) 32 (80)
NEMA 1 8536 SHG 2 (2) (3) (4) 105 (231)
NEMA 12 8536 SHA 2 (2) (3) (4) 106 (233)
7 – – 300 220 600 450 600 450 810 Open 8536 SJO 2 (2) (3) (4) 61 (135)
NEMA 1 8536 SJG 2 (2) (3) (4) 130 (287)
NEMA 12 8536 SJA 2 (2) (3) (4) 140 (309)
(1) Open: no enclosure (“O”).
NEMA 1: General purpose enclosure (“G”).
NEMA 12: Dust-tight and drip-tight industrial-use enclosure (“A”).
(2) Standard control circuit voltage:
Volts 24 110 120 208 220 240 380 440 480 550 600
50 Hz – V02 – – V03 – V05 V06 – V07 –
60 Hz V01 – V02 V08 – V03 – – V06 – V07
24 V and 120 V coils require the addition of form "S" for separate control. Example: 8536 SAO 12 V01 H10S.
(3) For optional variants, see pages 1/10 to 1/13.
(4) To complete the "H" code for solid-state overload relays, see page 1/10.
8536 SAO 12 V02 H20
531008
General, characteristics:
pages 1/4 and 1/5
Dimensions:
pages 1/14 to 1/17