Brochure

7/20
7
References
Accessories for Heavy Industrial
NEMA Style Controls 0
Power-pole adder kits, Timer attachments,
Control circuit fuse holders,
Transient suppression modules
Power-pole adder kits
One single- or double-circuit power pole kit may be field added to a basic 2- or 3-pole Type S contactor or starter, Size 0–2, or a
30–60 A lighting contactor. The ratings for these power-pole adders correspond to the NEMA contact ratings found in the contactor
and starter section or lighting contactor section. A 2- or 3-pole contactor or starter will accept only one single- or double-circuit
unit. A power pole cannot be used on 4- or 5-pole devices or devices which are mechanically interlocked.
For adding a power pole to a Size 2 or 60 A device, a coil change is required. When adding Sizes 0 to 2 power pole kits to a Size 3
to 7 or 100 to 800 A device, an adapter bracket (9999 SBT 1) is required.
The Class 9999 Types SB 6 to SB 15 power pole kits are suitable for copper wire only. Types SB 21 to SB 25 are supplied with
lugs suitable for copper and aluminum wire.
Description For use with Reference Weight
kg (lb)
Class Type NEMA Size or current rating
1 N/O power-
pole adder
8502, 8702, 8536,
8736, 8903
SB, SC, SM 0, 1 and 30 A 9999 SB 6
SD 2 9999 SB 11 (1)
SP 60 A 9999 SB 21 (1)
1 N/C power
pole adder
8502, 8702, 8536,
8736, 8903
SB, SC, SM 0, 1 and 30 A 9999 SB 7
SD 2 9999 SB 12 (1)
SP 60 A 9999 SB 22 (1)
1 N/O and 1 N/C
power-pole
adder
8502, 8702, 8536,
8736, 8903
SB, SC, SM 0, 1 and 30 A 9999 SB 8
SD 2 9999 SB 13 (1)
SP 60 A 9999 SB 23 (1)
2 N/O power-
pole adders
8502, 8702, 8536,
8736, 8903
SB, SC, SM 0, 1 and 30 A 9999 SB 9
SD 2 9999 SB 14 (1)
SP 60 A 9999 SB 24 (1)
2 N/C power
pole adders
8502, 8702, 8536,
8736, 8903
SB, SC, SM 0, 1 and 30 A 9999 SB 10
SD 2 9999 SB 15 (1)
SP 60 A 9999 SB 25 (1)
Adapter bracket
Description For use with Reference Weight
kg (lb)
Class Type NEMA Size or current rating
Adapter bracket 8502, 8702, 8536,
8736, 8903
SE to SJ and
SQ to SZ
3 to 7 and
100 to 800 A
9999 SBT 1
Control circuit fuse holders
The control circuit fuse holder is designed to be used on Type S contactors and starters, Sizes 00 to 7, when either one or two
control circuit fuses, 600 V maximum, are required. The Type SF 3 and SF 4 fuse holders accept standard 600 V Bussmann Type
KTK or equivalent fuses (10 mm x 38 mm), 6 A maximum. Type SFR 3 and SFR 4 fuse holders accept Class CC 600 V Bussmann
Type KTK-R or equivalent fuses only.
Type For use with Description (2) Reference Weight
kg (lb)
Class NEMA Size
Control circuit
fuse holders
8502, 8702, 8536,
8736
00 to 7 Single-fuse unit 9999 SF 3
Single-fuse unit for Class CC fuse 9999 SFR 3
Two-fuse unit 9999 SF 4
Two-fuse unit for Class CC fuses 9999 SFR 4
Transient suppression modules
The transient suppression module is designed to be used where the transient voltage, generated when opening the coil circuit,
interferes with the proper operation of nearby integrated or solid-state control circuits. The module consists of a RC circuit and is
designed to suppress the coil voltage transients to approximately 200% of peak coil supply voltage. The module is wired across
the coil for Type S, Sizes 00 to 5 and is designed for coil voltages of 120 V only.
Type For use with Reference Weight
kg (lb)
Class NEMA Size
Transient
suppression
modules
8502, 8702, 8536, 8736 00 to 2 9999 ST 1
3 to 5 9999 ST 2
(1) To order a Size 2 or 60 A power pole kit complete with a new starter coil, specify suffix Y118, plus the voltage and frequency.
Example: Class 9999 Type SB11 Form Y118, 120 volts, 60 Hz.
(2) Fuses not included.
9999 SB 6
DF531377
9999 SF 4
DF531379
9999 ST 1
DF531380