- SPX Cooling Technologies, Inc. CoolingTower Specification Sheet

Specifications
Marley
/
Sigma 1000/1200 Cooling Tower
/
Specifications: Options
28
Specification Value
Low Noise Tower:
1.1 Add the following at the end of this
paragraph: The cooling tower shall be
quiet operating, and shall produce an
overall level of sound no higher than ____
dBA at the critical location indicated on
the Plans.
Sound produced by a Sigma Steel tower operating in an unob-
structed environment will meet all but the most restrictive noise
limitations – and will react favorably to natural attenuation.
Where the tower has been sized to operate within an enclosure,
the enclosure itself will have a damping effect on sound. Sound
also declines with distance – by about 5 or 6 dBA each time
the distance doubles. Where noise at a critical point is likely to
exceed an acceptable limit, you have several options listed
below in ascending order of cost impact:
Where only a slight reduction in noise will satisfy — and the
source of concern is in a particular direction — merely turning
the tower may be the answer. Less sound emanates from the
cased face of the tower than does from the air intake face.
In many cases, noise concerns are limited to nighttime, when
ambient noise levels are lower and neighbors are trying to
sleep. You can usually resolve these situations by using two-
speed motors in either 1800/900 or 1800/1200 RPM configura-
tion; and operating the fans at reduced speed without cycling
“after hours”. (The natural nighttime reduction in wet-bulb tem-
perature makes this a very feasible solution in most areas of the
world, but the need to avoid cycling may cause the cold water
temperature to vary significantly.)
Variable speed drives automatically minimize the tower's noise
level during periods of reduced load and/or reduced ambient
without sacrificing the system's ability to maintain a constant
cold water temperature. This is a relatively inexpensive solution,
and can pay for itself quickly in reduced energy costs.
Where noise is a concern at all times (for example, near a hos-
pital), the best solution is to oversize the tower so it can operate
continuously at reduced (1200 or 900 RPM) motor speed even at
the highest design wet-bulb temperature. Typical sound reduc-
tions are 7 dBA at 2/3 fan speed or 10 dBA at 1/2 fan speed, but
larger reductions are often possible.
Extreme cases may require inlet and discharge sound attenu-
ator sections; however, the static pressure loss imposed by
attenuators may necessitate an increase in tower size. This is
the least desirable approach because of the significant cost
impact – and because of the obstruction to normal maintenance
procedures.
Y
our Marley representative can help you meet your sound
requirements.