Brochure
For a simplified “Quick Selection Guide,” request Form 40-109
Page 34 – Bulletin 40-10
For New Systems and Clean-Up After Burnout
Suction Line Filter-Drier Specifications
*Denotes TEMPORARY INSTALLATION. Cores for system clean-up; RPE-48-BD or RPE-100 Filter Elements are to be installed after clean-up.
Rated in accordance with ANSI/AHRI Standard 730.
REFRIGERANT 134a 22 404A & 507 407C 410A
EVAPORATOR TEMP. 40°F 20°F 0°F 40°F 20°F 0°F -20°F -40°F 20°F 0°F -20°F -40°F 40°F 40°F
PRESSURE DROP (psi) 2.0 1.5 1.0 3.0 8.0* 2.0 1.5 1.0 0.5 2.0 1.5 1.0 0.5 3.0 8.0* 3.0 8.0*
RSF-487-T 6.4 4.2 2.5 10.1 17.5 6.3 4.1 2.5 1.2 6.1 4.0 2.3 1.2 10.0 17.3 12.6 21.9
RSF-489-T 7.8 5.1 3.1 12.2 21.1 7.6 5.0 3.0 1.5 7.3 4.8 2.8 1.4 12.0 20.7 15.3 26.4
RSF-4811-T 9.4 6.2 3.7 14.8 25.6 9.3 6.1 3.6 1.8 8.9 5.8 3.4 1.7 14.6 25.3 18.5 32.0
RSF-4813-T 10.1 6.7 4.0 15.9 27.5 10.0 6.5 3.9 1.9 9.6 6.2 3.6 1.8 15.7 27.2 19.9 34.4
RSF-4817-T 11.0 7.2 4.4 17.2 29.8 10.8 7.1 4.2 2.1 10.4 6.8 3.9 2.0 17.0 29.4 21.5 37.3
RSF-4821-T 11.9 7.8 4.7 18.6 32.2 11.6 7.6 4.6 2.3 11.2 7.3 4.3 2.2 18.4 31.6 23.3 40.3
RSF-9617-T 16.1 13.0 8.1 29.7 49.0 19.8 13.7 8.7 4.7 17.9 12.2 7.6 4.0 28.6 47.2 37.1 61.3
RSF-9621-T 18.7 13.0 8.1 29.7 50.7 19.8 13.7 8.7 4.7 17.9 12.2 7.6 4.0 28.9 49.8 37.1 61.3
RSF-9625-T 19.2 13.0 8.1 30.0 51.9 20.0 13.7 8.7 4.7 17.9 12.2 7.6 4.0 29.7 51.0 37.5 63.4
C-30013-G 16.9 11.0 6.7 26.6 46.0 16.7 10.9 6.5 3.2 16.0 10.3 6.2 3.1 26.3 42.8 33.3 64.9
C-30017-G 17.2 11.1 6.8 27.0 46.7 16.9 11.1 6.6 3.3 16.2 10.4 6.3 3.1 26.7 43.3 33.8 58.4
C-40017-G 21.0 13.6 8.3 32.9 56.9 20.6 13.5 8.1 4.0 19.8 12.8 7.2 3.8 32.4 52.8 41.1 71.1
C-40021-G thru
C-40033-G
21.0 13.6 8.3 32.9 56.9 20.6 13.5 8.1 4.0 19.8 12.8 7.2 3.8 32.4 52.8 41.1 71.1
REFRIGERANT 134a 22 404A 407C 410A
EVAPORATOR TEMP. 40°F 20°F 0°F 40°F 20°F 0°F -20°F -40°F 20°F 0°F -20°F -40°F 40°F 40°F
PRESSURE DROP (psi) 2.0 1.5 1.0 3.0 2.0 1.5 1.0 0.5 2.0 1.5 1.0 0.5 3.0 3.0
C-083-S-T-HH 1.3 0.9 0.5 2.1 1.3 0.9 0.5 0.2 1.2 0.8 0.5 0.2 2.0 2.7
C-084-S-T-HH 1.4 1.0 0.6 2.1 1.4 1.0 0.6 0.3 1.3 0.9 0.5 0.3 2.1 2.8
C-164-S-T-HH 1.7 1.1 0.7 2.7 1.7 1.1 0.7 0.3 1.6 1.0 0.6 0.3 2.7 3.6
C-165-S-T-HH 2.0 1.3 0.8 3.2 2.0 1.3 0.8 0.4 1.9 1.2 0.7 0.4 3.2 4.2
C-166-S-T-HH 2.6 1.7 1.0 4.0 2.5 1.6 1.0 0.5 2.4 1.6 0.9 0.5 3.9 5.2
C-167-S-T-HH 2.8 1.8 1.1 4.5 2.8 1.8 1.1 0.5 2.7 1.7 1.0 0.5 4.4 5.9
C-305-S-T-HH 2.2 1.4 0.8 3.4 2.1 1.4 0.8 0.4 2.0 1.3 0.8 0.4 3.4 4.4
C-306-S-T-HH 2.8 1.8 1.1 4.4 2.8 1.8 1.1 0.5 2.7 1.7 1.0 0.5 4.4 5.8
C-307-S-T-HH 3.4 2.2 1.3 5.3 3.3 2.2 1.3 0.6 3.2 2.0 1.2 0.6 5.3 7.0
C-309-S-T-HH 3.8 2.4 1.5 5.9 3.7 2.4 1.5 0.7 3.6 2.3 1.4 0.7 5.8 7.7
C-417-S-T-HH 3.8 2.5 1.5 6.0 3.8 2.5 1.5 0.7 3.6 2.3 1.4 0.7 6.0 7.9
C-419-S-T-HH 4.0 2.6 1.6 6.2 3.9 2.5 1.5 0.8 3.7 2.4 1.5 0.7 6.1 8.0
C-437-S-T-HH 5.1 3.3 2.1 8.0 5.0 3.3 2.0 1.0 4.8 3.1 1.9 0.9 7.9 10.4
C-439-S-T-HH 6.4 4.2 2.5 10.0 6.3 4.1 2.5 1.2 6.0 3.9 2.4 1.2 9.9 13.1
C-4311-S-T-HH 7.1 4.6 2.8 11.1 6.9 4.6 2.7 1.4 6.7 4.3 2.6 1.3 10.9 14.4
C-4313-S-T-HH 7.8 5.1 3.1 12.2 7.6 5.0 3.0 1.5 7.3 4.7 2.9 1.4 12.0 15.9
C-607-S-T-HH 4.2 2.7 1.7 6.7 4.2 2.7 1.6 0.8 4.0 2.6 1.6 0.8 6.6 8.7
C-609-S-T-HH 4.8 3.1 1.9 7.6 4.7 3.1 1.8 0.9 4.5 2.9 1.8 0.9 7.4 9.8
Flow Capacity - Sealed Type Tons
■
°F
■
psi
Flow Capacity - Replaceable Core Type Tons
■
°F
■
psi
SELECTION INSTRUCTIONS
Except for the values in bold (R-22/R-
407C/R-410A at 40°F/4°C; 8 psi/0.55 bar
pressure drop), the flow capacities are
rated at the maximum recommended
pressure drop for permanent installation.
To ensure the suction line filter-drier
has ample contaminant removal ability,
selection must be based on flow capacity
and the amount of desiccant required for
system clean-up. The suction line filter-
drier must be large enough to adequately
remove acid, moisture and solid contami-
nants without causing nuisance plug-ups.
Sizing is especially important for sealed
type suction line filter-driers since they
should be sized to clean a small system
with one service call.
To reduce the pressure drop through
replaceable core shells, substitute cores
with filter elements (see page 24) after the
system has been cleaned up. The 6171-5
screen should be discarded when cores
are replaced with RPE-48-BD elements in
RSF shells.