Liquid Line
Ratings and Selection Recommendations
Replaceable Core Type Refrigerant 404A & 507
NOTE: The variation in flow ratings of filter-driers having the same size core and shell is caused by the difference in connection sizes used. Installing
the secondary filter in C-480 through C-19200 Series shells reduces the flow capacity by approximately 5 percent. R-502 water capacities are similar to
R-404A and R-507.
TYPE
SURFACE
FILTERING
AREA
RATINGS AT AHRI STANDARD CONDITIONS SELECTION RECOMMENDATIONS (Tons)
WATER CAPACITY
DROPS AT 60 PPM
REFRIGERANT
FLOW CAPACITY
REFRIGERATION AIR CONDITIONING
Sq.
Inch
cm
2
75°F
25°C
125°F
50°C
Tons at
1 psi ∆P
kW at
0.07 bar ∆P
Commercial &
Low Temperature
Equipment
O.E.M.
Self
Contained
Field Replacement
or Field Built-Up
Systems
RCW-42 (High Water Capacity Core)
C-R424-G
67 432
1049 853
7.6 26.7 5 7-1/2 7-1/2
C-R425-G 9.1 31.9
5 7-1/2 7-1/2
C-R427-G 12.4 43.5
RCW-48 or RCW-100 (High Water Capacity Cores)
C-485-G
64
413
1290 1049
9.8 34.4 7-1/2 10 7-1/2
C-487-G 16.0 56.2 10 12 10
C-489-G 28.9 101.4 10 20 10
C-967-G
128 826 2580 2098
26.2 92.0 15 20 15
C-969-G 32.6 114.4 25 30 25
C-1449-G
192 1239 3870 3147
39.7 139.3 30 35 30
C-14411-G 44.8 157.2 35 40 35
C-19211-G
256 1652 5160 4196
56.3 197.6 50 50 50
C-19213-G 66.2 232.4 55 60 55
C-19217-G 69.5 243.9 60 65 60
C-30013-G 294 1897 7890 6417 74.5 261.5 70 80 70
C-40017-G 392
2529
10520 8556 96.8 339.8 100 125 100
RC-4864 or RC-10098 (Standard Cores)
C-485-G
64
413
408 309
9.8 34.4 7-1/2 10 7-1/2
C-487-G 16.0 56.2 10 12 10
C-489-G 28.9 101.4 10 20 10
C-967-G
128 826 816 618
26.2 92.0 15 20 15
C-969-G 32.6 114.4 25 30 25
C-1449-G
192 1239 1224 927
39.7 139.3 30 35 30
C-14411-G 44.8 157.2 35 40 35
C-19211-G
256 1652 1632 1236
56.3 197.6 50 50 50
C-19213-G 66.2 232.4 55 60 55
C-19217-G 69.5 243.9 60 65 60
C-30013-G 294 1897 2631 1992 74.5 261.5 70 80 70
C-40017-G 392
2529
3508 2656 96.8 339.8 100 125 100
For suction line
filter-driers
see page 30
For sealed model
Catch-Alls
see page 10