User Guide
This  technique  may  be  carried  further  by  using  additional 
evaporator sections, each controlled by a separate TEV and 
refrigerant  distributor.  Using  multiple  evaporator  sections 
will let highly reduced loads to be properly controlled.
Single Evaporator Controlled by Two TEVs
For evaporator coils which are not split by design, i.e., row 
split, face split, or interlaced, the following techniques may 
be employed to improve part-load operation.
Figure 10 illustrates the use of two TEVs and two distribu-
tors feeding a  single  evaporator. Each evaporator  circuit  is 
fed  by  two  distributor  circuits,  one  from  each  distributor. 
The solenoid valves are connected to the compressor capac-
ity modulating system as mentioned before. Using this con-
figuration, TEV and distributor capacities can be reduced in 
three stages. As an example, assume that TEV and distribu-
tor combination  A  are sized  to  handle 67%  of the  load  and 
combination B 33% of the load. The three stages of valve and 
distributor capacity reduction result from opening or closing 
the solenoid valves according to the following table:
Another  variation  of  this  technique  is  to  have  each  evapo-
rator circuit fed  by  a single distributor  circuit  and size the 
TEVs  and  distributors  on  the  expected  load  of  the  total 
number  of  circuits  fed  by  each  TEV.  Reducing  evaporator 
capacity  is  accomplished  by  closing  a  solenoid  valve  which 
deactivates the circuits being fed by the TEV and distributor 
downstream of  the  solenoid  valve.  This  method  of  capacity 
control,  however,  requires  a  degree  of  care  since  the  heat 
load on the evaporator circuits will be affected in the manner 
in which circuits are deactivated.
The Types  (E)BF and  EBS  valves feature  a single  pushrod 
which extends  through the  port  of the  valve. See  Figure 8. 
The port and pushrod cross sectional areas are identical so 
that  the  opening  force  created  by  pressure  drop  across  the 
port  is  canceled  by  the  pressure  drop  across  the  pushrod. 
Furthermore,  excellent  pin  and  port  alignment  is  provided 
by this design. Refer to the section, Effect of Pressure Drop 
Across the Valve Port, on Page 4 for additional information.
The Type (E)BF  valve  with the ‘AA’  port was developed by 
Sporlan in 1988. Its original design used a two pushrod con-
struction similar to the conventional Type F valve, and the 
balanced design was achieved by the use of a third floating 
rod located above the valve port. As with the single rod bal-
anced port construction, the floating rod causes the pressure 
drop across it to offset the opening force created by the pres-
sure drop across the port.
The ‘AA’ port Type (E)BF valve was later redesigned in 1993 
to a  single pushrod  construction like  the other  Type (E)BF 
valve sizes. All ‘AA’ port valves carrying a ‘3393’ date code or 
later will have the single pushrod construction.
System Design For Part-Load Conditions
On systems where the compressor can unload to 50 percent 
of its rated capacity, care must be exercised when selecting 
expansion  valves  and  refrigerant  distributors.  If  the  com-
pressor  can  unload  below  33  percent  of  its  rated  capacity, 
special  design  considerations  may  be  necessary  to  assure 
proper TEV operation. Figures 9, 10, and 11 are piping sche-
matics illustrating  three  possible methods  of balancing  the 
capacity of the TEV and distributor with the compressor dur-
ing low load operation. Recognized piping references such as 
the equipment  manufacturer’s  literature  and  the ASHRAE 
Handbooks  should  be  consulted  for  further  information  on 
this  subject.  Sporlan  cannot  be  responsible  for  dam-
ages  arising  from  improper  piping  practices  or  the 
improper use of its products.
Two or More Evaporator Sections Handling the 
Same Load
Figure 9 illustrates two parallel evaporators each controlled 
by a separate TEV and refrigerant distributor. Each evapo-
rator  shares  half  of  the  total common  load.  The  liquid  line 
solenoid  valve  ahead  of  each  TEV  is  electrically  connected 
to  the  compressor  capacity  modulating  system.  When  the 
compressor capacity is reduced to 50%, one of the two sole-
noid valves closes stopping refrigerant flow to one TEV. The 
TEV remaining in operation will then have a rated capacity 
approximately  equal  to  the  compressor  capacity  operating 
50% unloaded.
BULLETIN 10-9 / Page 11 
rosserpmoC
yticapaC
lluFfotnecreP
yticapaC
fonoitisoP
dioneloS
evlaV A""
fonoitisoP
dioneloS
evlaV B""
dnaevlaVlatoT
gnitubirtsiD
gnidaoL
fotnecreP
yticapaCdetaR
%001
nepO
nepO
%001
%38 83%
%76
desolC
%001
%05 75%
%33
desolC Open
%001
%61 50%
TEV and Distributor
Solenoid
Valve
Solenoid
Valve
Capacity Reduction – 2 or more evaporator sections
handling same load.
TEV and Distributor
Figure 9
Solenoid 
Valve
"A"
TEV and Distributor
"A"
TEV and Distributor
"B"
Solenoid
Valve
"B"
Capacity Reduction – Single evaporator controlled with
 2 TEVs and 2 Solenoid Valves.
Figure 10
Table 4










