User Guide
BULLETIN 10-9 / Page 15 
When  a  Sporlan  TEV  is  properly  selected  and  applied,  the 
factory superheat setting  will  usually provide an  operating 
superheat in the range of 8 to 12°F. A precise determination 
of the  valve’s  operating superheat  from a  factory  setting is 
not  possible  since  factory  settings  are  determined  on  the 
basis of static superheat, and opening superheat of the valve 
is  influenced  by  several  design  factors  within  the  system. 
Once  the  TEV  has  been  placed  on  the  system  and  set  to 
the desired operating superheat, however, the valve’s static 
superheat can be measured on a test fixture permitting the 
desired setting to be duplicated for production runs.
All  Sporlan  TEVs  have  reserve  capacity  in  addition  to  the 
capacity  shown  in  the  rating  tables  in  Bulletin  10-10.  This 
reserve  capacity  should  not  be  considered  when  selecting  a 
valve  and,  in most cases,  will  not  be  utilized  if the  valve  is 
properly  selected  and  applied.  Reserve  capacity,  however, 
is  an  important  and  necessary  characteristic  of  any  well 
designed  TEV.  Reserve  capacity  enables  the valve  to  adjust 
for  a  temporary  increase  in  load,  periods  of  low  condensing 
pressure, and moderate amounts of flash gas in the liquid line.
Valve Setting
All  Sporlan  TEVs  will  produce  rated  capacity  at  the  stan-
dard  factory  setting.  If  the  valve  adjusting  stem  is  turned 
clockwise,  the  additional  spring  pressure  created  will 
increase static superheat  and decrease the  valve’s  capacity 
to  a  limited  degree.  Turning  the  adjusting  stem  counter-
clockwise  will  decrease  static  superheat  and  increase  the 
valve’s capacity to a limited degree. Figure 14 illustrates the 
effect setting has on valve capacity.
Referring to Gradient Curve A in Figure 14, Capacity C2 is 
achieved with a static superheat setting of A and an operat-
ing  superheat  of  C.  Turning  the  adjusting  stem  clockwise 
will  increase  the  static  superheat  and  shift  the  curve  to 
the right. This new curve, identified as Gradient Curve B, 
shows  that  valve  capacity  will  decrease  to  capacity  C1  at 
the  same  operating superheat  C. Capacity C2  can  only  be 
achieved  at  the  expense  of  a  higher  operating  superheat 
designated as D.
On  an  operating  system  where  a  given  valve  capacity  is 
required,  any  valve  adjustment  will  merely  change  the 
superheat at which the valve is operating.
Evaporator Temperature
The  pressure-temperature  curves  for  all  refrigerants  have 
a flatter slope  at lower temperatures.  Figure 15 illustrates 
a P-T curve using R-22 as an example. The P-T curve for a 
thermostatic  charge  will  also  be  flatter  at  lower  tempera-
tures. As a result, a given bulb temperature change causes 
a  smaller  bulb  pressure  change  at  lower  evaporator  tem-
peratures.  A  given  change  in  superheat  will  result  in  less 
pressure  difference  across  the  valve  diaphragm  at  lower 
evaporating temperature causing a reduction in valve open-
ing and valve capacity.
Subcooling
Subcooling is defined as the difference between the refriger-
ant liquid temperature and its saturation temperature. For 
example, the amount of subcooling of R-22 liquid at 85°F and 
196 psig is calculated as follows:
saturation temperature of R-22 liquid at 196 psig = 
100°F subcooling = 100°F - 85°F = 15°F
Adequate  subcooling  of  the  refrigerant  liquid  is  necessary 
to  prevent  the  formation  of  liquid  line  vapor  due  to  pres-
sure losses in the liquid line. Vapor in the liquid line, even 
in small quantities, will  measurably  reduce valve capacity. 
Several methods by which liquid line vapor can be prevented 
in  spite  of  relatively  high  liquid  line  pressure  losses  are 
explained in Bulletin 10-11.
Pressure - psig
Temperature - °F
Refrigerant - 22
Pressure - Temperature
70
10 20 40
30
50
∆ P = 7.1 psi
∆ P = 5.0 psi
5°F
5°F
30
tnaregirfeR
a431,21 25 psi
705,205,A404,22 35 psi
A014 45 psi
)ainommA(717 40 psi
*Average Pressure Drop Across Distributor
Superheat
Valve Capacity
0
B
A & B Static Superheat
C & D 
Operating Superheat 
Capacity C2
Full Open
Capacity
Capacity C1
A
C
D
Gradient Curve - A
Gradient Curve - B
Figure 14
Figure 15
tnaregirfeR
teeF–tfiLlacitreV
02 04 06 08 001
isp–ssoLerusserPcitatS
12 11 22 33 44 55
A404,22 01 02 30 39 49
205,a431 01 02 03 04 50
A014 9 71 62 43 43
705 8 71 52 43 42
)ainommA(717 5 01 51 02 25
Table 8
Table 9
*See Sporlan Bulletin 20-10 for pressure drop data as related to percent loading.










