User Guide
ing  the  evaporator,  which  is  usually  termed  hunting  or 
cycling. The amount of hunting in a system is influenced by 
the design of the evaporator coil, suction line piping at the 
valve’s sensing bulb location, and the variability of the heat 
load  on  the  evaporator.  Hunting  may  cause  a  reduction  in 
total system capacity, and a noticeable variation of evapora-
tor pressure on systems having one evaporator. If hunting is 
severe, occasional floodback may result.
To  help  reduce  or  eliminate  valve  hunting,  many  Sporlan 
pressure  limiting  thermostatic  charges  feature  the 
FLOWMASTER  design  introduced  by  Sporlan  in  1948. 
This design incorporates a thermal ballast with the charge 
to help stabilize valve control.
Originally,  it  was  felt  that  a  highly  temperature  sensitive 
TEV  would  best  be  able  to  reduce  hunting.  This  concept 
has proved to be incorrect for the majority of air condition-
ing  and  heat  pump  applications  and,  in  fact,  it  was  found 
to  often  aggravate  hunting  problems.  A  less  temperature 
sensitive TEV using specifically designed pressure limiting 
thermostatic charges has proven to be the best solution for 
these applications.
Type  VGA  Thermostatic  Charge  —  The  VGA  charge  is 
a  specially  designed  pressure  limiting  charge  for  R-22  air 
conditioning and  heat  pump  applications.  The constituents 
and  thermal  ballast  used  with  this  thermostatic  charge 
provide exceptional  anti-hunt characteristics,  which makes 
it the recommended charge for the majority of these applica-
tions. Due to its design, the MOP of the VGA charge is not 
as  defined  as  the  VCP100  charge,  our  alternate  standard 
thermostatic  charge  for  R-22  air  conditioning  and  heat 
pump  applications.  Therefore,  if  a  defined  MOP  is  not 
required, the VGA charge may be used in place of the 
VCP100 charge.
Maximum  operating  pressures  for  standard  Sporlan  pres-
sure limiting  charges are  listed  in  Table  3.  The  factory air 
test  pressure  represents  the  valve  MOP  determined  by  a 
Sporlan air test fixture. The nominal system pressure is the 
actual  system  MOP.  If  an  application  requires  a  pressure 
limiting charge with an MOP not shown, contact Sporlan for 
assistance.
Due to the design of pressure limiting charges, the valve dia-
phragm and capillary tubing must be kept at a temperature 
warmer than the bulb during system operation. Otherwise, 
migration of the charge away from the bulb will occur, and 
cause loss of valve control.
A  properly  selected  and  applied  pressure  drop  type  dis-
tributor is effective in preventing charge migration. Figure 7 
illustrates how the pressure drop across this type of distribu-
tor keeps the TEV  outlet pressure and temperature  higher 
than the suction gas temperature.
Pressure drop  at  the refrigerant  distributor  does not  affect 
system  capacity.  The  refrigerant  distributor  simply  lowers 
the pressure drop across the TEV by a small amount. If the 
TEV  is  properly  sized,  it  will  maintain  desired  superheat 
(and  system  capacity)  with  the  remaining  pressure  drop 
available to the valve.
When  applying  a  TEV  and  distributor,  the  two  compo-
nents perform  together to  provide stable  system operation. 
Application  of  these  components  is  much  more  critical  on 
systems  that  operate  at  part-load  conditions  much  of  their 
operating  time,  e.g.,  variable  air  volume  (VAV)  systems 
and  refrigeration  systems  with  compressor  unloading.  See 
Bulletin  20-10  for  complete  information  on  refrigerant 
distributors.
Refrigeration Applications
Ordinary refrigeration applications may be divided into the 
following  three  categories:  commercial  refrigeration,  low 
temperature  refrigeration,  and  extremely  low  temperature 
refrigeration.  For  each  of  these  categories,  Sporlan  has 
developed a Selective Charge to provide optimum valve per-
formance. These charges are described below.
Type C Charges — The charges listed under the commer-
cial refrigeration section in the Recommended Thermostatic 
Charges  table  on  Page  18  are  collectively  known  as  C 
Charges.  These  charges  are  liquid-cross charges  and  have 
an  operating  range  from  an  evaporating  temperature  of 
50°F  to   –10°F.  Figure  6  illustrates  a  typical  superheat 
characteristic  curve  of  the  C  Charge.  For  comparison 
purposes,  the  superheat  characteristic  curve  of  a  straight 
liquid  charge  is  also  shown.  The  flatter  curve  of  the  C 
Charge allows  the  valve  to  respond in a  more  stable man-
ner  to  changes  in  evaporator  pressure.  Depending  on  the 
static superheat requirements, the Type C Charge has been 
applied by  some  manufacturers to  display cases operating 
at both medium and low temperature.
Types  Z  and  ZP  Charges  —  The  charges  listed  under 
the  low  temperature  refrigeration  section  are  the  Types  Z 
and  ZP  Charges.  The  Z  Charges  (FZ,  VZ,  SZ,  RZ,  and  PZ) 
are liquid-cross charges having an operating range from an 
evaporating  temperature  of  0°F  to  –40°F.  A  typical  super-
heat  characteristic  curve  of  the  Z  Charge  is  illustrated  in 
Figure  6.  Since  the  curve  slopes  upward  to  the  right,  the 
valve  will  control  at  lower  superheat  values  as  evaporator 
temperature decreases, providing operational advantages for 
low  temperature refrigeration. This  characteristic prevents 
Page 8 / BULLETIN 10-9 
R-22
196 psig
(100°F)
P
1 
= 94 psig
 (56°F)
P
2
 = 69 psig
 (40°F)
66 psig (Superheat to 50°F)
66 psig
(38°F)
tnaregirfeR egrahCcitatsomrehT
-POM igsp
yrotcaF
tseTriA
lanimoN
metsyS
21
06PCF 60 50
PCF 40 30
PZF 20 12
22
001PCV 100 90
AGV
* *
PCV 65 55
04PZV 40 30
a431
06PCJ 60 50
PCJ 40 30
A404
511PCS 115 105
PCS 75 65
PZS 45 35
205
511PCR 115 105
PCR 75 65
PZR 45 35
705 PZP 45 35
* s.noitidnocgnitarepolamronevobA
Figure 7
Table 3










