User Guide
and subtracting the saturation temperature from the vapor 
temperature  measured  at  the  sensing  bulb  location.  For 
example, the superheat of R-22 vapor at 50°F and 68.5 psig 
at the sensing bulb location is calculated as follows:
saturation  temperature  of  R-22  vapor  at  68.5  psig  =  40°F 
superheat = 50°F - 40°F = 10°F
Another method of measuring superheat the TEV is control-
ling  is  the  two  temperature  method.  With  this  method, 
saturation  temperature  is  measured  directly  by  placing  a 
temperature  probe  on  the  evaporator  surface,  normally  at 
a  location  one-half  to  two-thirds  the  distance  through  the 
evaporator coil. Since this method can only approximate true 
saturation temperature, it is not as reliable as the pressure-
temperature  method,  and  it  should  be  avoided  whenever 
possible.
The  TEV  is  designed  to  control  superheat  at  a  constant 
value at the location of its sensing bulb. The level of super-
heat  determines  to  what  extent  the  valve  is  open.  A  TEV 
controlling  at  a  high  superheat  will  be  further  open  than 
a TEV controlling  at  a low superheat.  Refer to the  section, 
How  the  Thermostatic  Expansion  Valve  Works,  on  Page  3 
for additional  information.  Figure 13  shows  a  plot  of valve 
capacity  versus  superheat  for  a  typical  TEV,  illustrating 
the effect superheat has on valve capacity. For the purpose 
of  understanding  the  relationship  between  superheat  and 
valve capacity, superheat may be described as follows:
Static  Superheat  —  static  superheat  is  the  amount  of 
superheat  necessary  to  overcome  the  spring  and  equalizer 
pressures  so  that  any  additional  superheat  will  cause  the 
valve to open.
Opening Superheat — opening superheat is the amount of 
superheat required to move the valve pin away from the seat 
after the spring and equalizer pressures have been overcome 
to permit refrigerant flow.
Operating Superheat — operating superheat is the super-
heat at  which the  TEV operates  on a  refrigeration system. 
Operating superheat is the sum of static and opening super-
heats. The valve capacity versus operating superheat curve 
is referred to as the valve gradient.
The most desirable operating superheat for a particular sys-
tem largely depends on the temperature difference (TD) 
between the refrigerant and  the medium being cooled.  The 
basic definition  of  TD  is  the difference  between  evaporator 
temperature  and  the  entering  temperature  of  the  medium 
being cooled, i.e., air or water. Systems with a high TD, such 
as  air  conditioning  and  heat  pump  systems,  can  tolerate 
higher superheats without appreciable loss in system capac-
ity. Refrigeration and low temperature systems require low 
superheats due to their lower TDs. The table below provides 
general  recommendations  for  superheat  settings  for  differ-
ent  evaporator  temperature  ranges.  These  settings  are 
only estimates for typical system designs and should 
only  be  used  if  setting  guidelines  are  unavailable 
from the system manufacturer:
Page 14 / BULLETIN 10-9 
serve as  a secondary  orifice  to reduce  pressure drop  across 
the valve port.
Thermostatic Charges for Ammonia Valves
Thermostatic charges C, Z, and L are available for the Type 
D  thermostatic  expansion  valve.  The  Type  L  thermostatic 
charge is the only charge available for the Type A valve.
The Types C and Z thermostatic charges provide operating 
advantages  for  systems  that  cycle  in  response  to  a  suction 
pressure  switch  or  thermostat.  These  charges  are  also  rec-
ommended  for  systems  using  a  small  capacity  compressor. 
The  table  below  lists  the  recommended  temperature  range 
for each charge.
Cold storage plants will often have large centralized ammo-
nia systems. These systems will consist of many evaporators 
connected  to  one  or  more  large  compressors.  With  many 
thermostatic expansion valves operating at a common evapo-
rator pressure, a change in flow rate made by one valve will 
not  have  a  significant  effect  on  the  evaporator  pressure. 
This  operating  characteristic  makes  it  more  desirable  for 
the  thermostatic  expansion  valve  to  be  more  responsive  to 
changes in bulb temperature. This is the feature of the Type 
L  charge.  Therefore,  for  large  ammonia  systems  consisting 
of multiple evaporators, the Type L charge is recommended.
FACTORS AFFECTING TEV OPERATION AND 
PERFORMANCE
Many factors exist which influence TEV operation and per-
formance. The following discussion lists the major factors:
Superheat
Superheat  is  defined  as  the  difference  between  the  refrig-
erant  vapor  temperature  and  its  saturation  temperature. 
To properly  measure  the superheat  the TEV  is controlling, 
the pressure-temperature  method is  used. This  method 
consists  of  measuring  the  suction  pressure  at  the  sensing 
bulb  location,  converting  this  pressure  to  its  saturation 
temperature  by  using  a  pressure  temperature  (P-T)  chart, 
sgnitteStaehrepuSrofsenilediuGlareneG
noitacilppA 
riA
gninoitidnoC
pmuPtaeH&
laicremmoC
noitaregirfeR
woL
erutarepmeT
noitaregirfeR
rotaropavE
erutarepmeT °F
50° to 40° 40° to 0° 0° to –40°
taehrepuSdetsegguS
gnitteS °F
°8 °21ot °6 °8ot
4° to 6°
egrahCcitatsomrehT erutarepmeTrotaropavE F°
C 40° to 0°
Z 0° to –30°
For applications at evaporator temperatures below minus 30°F, consult Parker 
Refrigerating Specialties Division.
Rated
Capacity
Full Open
Capacity
Reserve
Capacity
Superheat
Valve Capacity
0
A B
C
A = Static Superheat
B = Operating Superheat
C = Operating Superheat
Figure 13
Table 6
Table 7










