Installation Guide

www.SpenceValve.com
Spence FTE Series Float and Thermostatic
Steam Trap
Introduction
This installation sheet covers the installation and
maintenance of FTE Series Float and Thermostatic
Steam Trap.
Product Description
The FTE Series ball oat traps are tted with an
integral balanced pressure type thermostatic air went.
The FTE Series is available with horizontal in line
connections. However, in case of FTE-14 sizes
NPS 1/2 and 3/4 / DN 15 and 20, the position of body
can be changed to suit di󰀨erent ow directions like
left to right, top to bottom or right to left. A steam lock
release (SLR) option is available to FTE Series Traps.
Specications
Available Congurations
See Table 1
End Connection Styles
NPT, CL125, CL150, CL300, CL600,
DIN 10, 16, 25 or 40 and BS10 - F, H, J, K or R
Maximum Operating Pressure
(1)
See Table 2
Maximum Operating Temperature
(1)
Saturated at pressure
Maximum Allowable Pressure
(1)
Cast iron and Ductile iron: 232 psig / 16 bar
Cast steel: 465 psig / 32 bar
Maximum Allowable Temperature
(1)
Cast iron and Ductile iron: 450ºF / 232ºC
Cast steel: 850ºF / 454ºC
Materials of Construction
Body and Cover: Cast iron, Ductile iron and
Cast steel
Valve, Valve Seat, Float, Lever Assembly,
Thermostatic Airvent and Housing:
Stainless steel
Cover Bolts: Carbon steel
Installation
WARNING
Personal injury, property damage,
equipment damage or leakage due
to escaping steam or bursting of
pressure containing parts may result
if this equipment is over pressured or
is installed where service conditions
could exceed the limits given in the
specifications or where conditions
exceed any ratings of the adjacent
piping or piping connections. To
avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate
code, regulation, or standard) to prevent
service conditions from exceeding
those limits.
The maximum differential pressure (ΔP)
stamped on product name plate must
be greater than the maximum pressure
differential across the trap.
1. The pressure/temperature limits in this Installation Sheet and any applicable standard or code limitation should not be exceeded.