User’s Manual Pub. 0300274-01 Rev. A.0
Input Specifications
Fusing
2.7 Ω 1/10 W resistor, 24 VDC input
0.47 Ω 1/10 W resistor, 3.3 VDC input
Input to backplane
isolation
707 VDC for 1 minute
Channel to channel
isolation
None
Fault detection
None
Wire size
#22 to #30 AWG (for the mating connector)
Operating temperature
-20 ºC to 65 ºC
Storage temperature
-40 ºC to 85 ºC
Operating humidity
5% to 95% (non-condensing)
Manufacturing
RoHS & REACH compliant
Dimensions
58.4 mm × 29.3 mm × 25 mm
Reliability
The Mean Time between Failure (MTBF) target for the 2080sc-BAC is 250,000
hours.