Manual

Table Of Contents
Chapter 4: Implementing the BACnet Protocol 4-3
User’s Manual Pub. 0300274-01 Rev. A.0
Properties Supported
Property Data
Type Identifier
Read/Write
Vendor_Identifier
Unsigned16
120
R
Model_Name
CharacterString
70
R
Firmware_Revision
CharacterString
44
R
Application_Software_Version
CharacterString
12
R
Protocol_Version
Unsigned
98
R
Protocol_Revision
Unsigned
139
R
Protocol_Services_Supported
BACnetServicesSupported
97
R
Protocol_Object_Type_Supported
BACnetObjectTypesSupported
96
R
Object_List
Sequence of
BACnetObjectIdentifier
76
R
Max_APDU_Length_Supported
Unsigned
62
R
Segmentation_Supported
BACnetSegmentation
107
R
Local_Time
Time
57
R
Local_Date
Date
56
R
UTC_Offset
Integer
119
R/W
APDU_Timeout
Unsigned
11
R
Number_Of_ADPU_Retries
Unsigned
73
R
Max_Master
Unsigned
64
R/W
Max_Info_Frames
Unsigned
63
R/W
Device_Address_Binding
Sequence of
BACnetAddressBinding
30
R
Database_Revision
Unsigned
155
R
The following table lists BACnet object types and properties supported by the
BACnet Communications Module.
Supported Object Types Properties
Property
Device
Binary Value
Analog Value
Object Identifier
Object Name
Object Type
System Status
Vendor Name
Vendor Identifier
Model Name
Firmware Revision