3-22 Chapter 3: Configuring the Module
User’s Manual Pub. 0300274-01 Rev. A.0
Examples: To write BO 3 present value to 1, do this “bacwp 200121 4 3 85 15 -
1 9 1”
{param 1} 200121. This is the module instance number.
{param 2} 0. This is the object type. Object type is defined as: BI (3),
BO(4), AI(0), AO(1).
{param 3} 3. This is the object instance.
{param 4} 85. This is the property (present value 85, property array 87,
object name 77, object list 76).
{param 5} 15. This is the priority. BACnet property write uses priority,
levels from 1 to 16. The module keeps a table for those priorities; high
priority overrides lower priority. So if there is a value in priority 14,
priority 15 value has no effect.
{param 6} -1. This is the index. Use -1 for a single property write.
{param 7} 9. Value type. Use 9 for BI and BO; use 4 for AI and AO.
{param 8} 1. Value. This is the actual value to be written to the tag.