Appendix A: Module Specifications A-3
User'sManualPub.030023101Rev.A
Voltage Accuracy
with 4.17 Hz filter
Accuracy
Limit At
°25C
Accuracy
Limit At 0-
°55C
Repeatability
Limit
At °25C & 4.17
Hz filter
±50 mV range ±20uV ±35uV ±10uV
±100 mV range ±40uV ±60uV ±13uV
0-5 V range ±2.5mV ±5mV ±1mV
1-5 V range ±2.5mV ±5mV ±1mV
0-10 V range ±5mV ±10mV ±1mV
±10 V range ±10mV ±20mV ±1mV
Current Accuracy
with 4.17 Hz filter
Accuracy
Limit At
°25C
Accuracy
Limit At 0-
°55C
Repeatability
Limit
At °25C & 4.17
Hz filter
0-20 mA range ±20uA ±40uA ±1uA
4-20 mA range ±20uA ±40uA ±1uA
Resistance Accuracy
with 4.17 Hz filter
Accuracy
Limit At
°25C
Accuracy
Limit At 0-
°55C
Repeatability
Limit
At °25C & 4.17
Hz filter
0-150 ohms range
±0.15
ohms ±0.25 ohms ±10 milliohms
0-1000 ohms range ±1.0 ohms ±2.0 ohms ±100 milliohms
0-3000 ohms range ±1.5 ohms ±2.5 ohms ±100 milliohms
RTD Accuracy
With 4.17 Hz filters
Accuracy
°C
Limit At
°25C
Accuracy
°C
Limit At
0°55C
Repeatability
Limit
At °25C & 4.17
Hz filter
Platinum 385 (100, 200, 500 and 1000
ohms) (IEC751 1983, Amend 2 1995;
JISC 1604 1997) ± 0.7 °C ± 1.2 °C ± 0.1 °C
Platinum 3916 (100, 200, 500 and 1000
ohms) (JISC 1604: 1981) ± 0.6 °C ± 1.1 °C ± 0.1 °C
Nickel 618 (100 ohms) (DIN 43760
Sept. 1987) ± 0.3 °C ± 0.5 °C ± 0.1 °C
Nickel 672(120 ohms) (DIN 43760
Sept. 1987) ± 0.3 °C ± 0.5 °C ± 0.1 °C
Nickel-Iron (518) (MINCO Application
Aid #18,Date 5/90) ± 0.4 °C ± 0.7 °C ± 0.1 °C
Copper 426 (10 ohms) (SAMA RC21-4-
1966) ± 2.4 °C ± 2.8 °C ± 0.1 °C
General Specifications
Voltage range
Supply current
24V dc nom
240 mA @ 24V dc
Dimensions (with module installed in
base)
HxWxD approx.
94 x 94 x 69 mm
(3.7 x 3.7 x 2.7 in.)
Environmental Conditions
Temperature, operating 0…55 °C (-32…131 °F)
Temperature, storage –40…85 °C (–40…185 °F)