User Manual

3-10 Flex™ IO Isolated Universal Input Module
User'sManualPub.030023101Rev.A
Table 3-2 (Fault Mode)
State Function
0 Disabled
1 Enable Broken Wire Detection
3.4.2 Input Type [Words 1 – 8 (Bits 0 to 4)]
Use the table below to select the input type for each channel.
Table 3-3 (Input Type)
Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Range:
0 0 0 0 0 B Type Thermocouple
0 0 0 0 1 C Type Thermocouple
0 0 0 1 0 E Type Thermocouple
0 0 0 1 1 J Type Thermocouple
0 0 1 0 0 K Type Thermocouple
0 0 1 0 1 N Type Thermocouple
0 0 1 1 0 R Type Thermocouple
0 0 1 1 1 S Type Thermocouple
0 1 0 0 0 T Type Thermocouple
0 1 0 0 1 100 Pt 0.385
0 1 0 1 0 200 Pt 0.385
0 1 0 1 1 500 Pt 0.385
0 1 1 0 0 1000 Pt 0.385
0 1 1 0 1 100 Pt 0.3916
0 1 1 1 0 200 Pt 0.3916
0 1 1 1 1 500 Pt 0.3916
1 0 0 0 0 1000 Pt 0.3916
1 0 0 0 1 10 Cu 0.426
1 0 0 1 0 100 Ni 0.618
1 0 0 1 1 120 Ni 0.672
1 0 1 0 0 604 NiFe 0.518
1 0 1 0 1 R 0 to 150
1 0 1 1 0 R 0 to 1000
1 0 1 1 1 R 0 to 3000
1 1 0 0 0 +/- 50 mV
1 1 0 0 1 +/- 100 mV
1 1 0 1 0 0 to 5V
1 1 0 1 1 1 to 5V
1 1 1 0 0 +/- 10V
1 1 1 0 1 0 to 10V
1 1 1 1 0 4 to 20 mA
1 1 1 1 1 0 to 20 mA
3.4.3 Input Filter [Words 1 – 8 (Bits 5 to 7)
Use the table below to select the appropriate filter for each channel.
Table 3-4 (Filter Settings)
Bit 7 Bit 6 Bit 5 ADC Filter:
0 0 0 4.17 Hz
0 0 1 10.0 Hz