4.2.4 Selecting Data Formats (Bits 12 through 14)
This selection configures channels 0 through 5 to present analog data in any of the
following formats:
• Raw/Proportional Data
• Engineering Units x 1
• Engineering Units x 10
• Scaled for PID
• Percent Range
Table 4-3 (Channel Data Word Format)
Input
Type
Data Format
Engineering Units x 10 Engineering Units x 1 Scaled
For
PID
Proportional
Counts
˚ Celsius ˚ Fahrenheit ˚ Celsius ˚ Fahrenheit
J -210 to 1200 -346 to 2192 -2100 to 12000 -3460 to 21920 0 to 16383 -32767 to 32767
K -270 to 1370 -454 to 2498 -2700 to 13700 -4540 to 24980 0 to 16383 -32767 to 32767
T -270 to 400 -454 to 752 -2700 to 4000 -4540 to 7520 0 to 16383 -32767 to 32767
E -270 to 1000 -454 to 1832 -2700 to 10000 -4540 to 18320 0 to 16383 -32767 to 32767
R 0 to 1768 32 to 3214 0 to 17680 320 to 32144 0 to 16383 -32767 to 32767
S 0 to 1768 32 to 3214 0 to 17680 320 to 32144 0 to 16383 -32767 to 32767
B 300 to 1820 572 to 3308 3000 to 18200 5720 to 32767
5
0 to 16383 -32767 to 32767
N -210 to 1300 -346 to 2372 -2100 to 13000 -3460 to 23720 0 to 16383 -32767 to 32767
C 0 to 2315 32 to 4199 0 to 23150 320 to 32767
5
0 to 16383 -32767 to 32767
L -200 to 900 -328 to 1652 -2000 to 9000 -3280 to 16520 0 to 16383 -32767 to 32727
+/- 50 mV -500 to 500
2
-500 to 500
2
-5000 to 5000
2
-5000 to 5000
6
0 to 16383 -32767 to 32767
+/- 100 mV -1000 to 1000
2
-1000 to 1000
2
-10000 to 10000
2
-10000 to 10000
6
0 to 16383 -32767 to 32767
Note: The engineering units data formats represent real engineering temperature
units provided by the module to the controller. The raw/proportional counts, scaled-
for-PID and percent of full-scale data formats may yield the highest effective
resolutions, but may also require that you convert channel data to real engineering
units in your control program.
Raw/Proportional Data
The value presented to the controller is proportional to the selected input and scaled into
the maximum data range allowed by the bit resolution of the A/D converter and filter
5
Type B and C thermocouples cannot be represented in engineering units x 1 (°F) above 3276.7°F. Software treats
it as an over range error.
6
When millivolts are selected, the temperature setting is ignored. Analog input data is the same for either °C or °F
selection.