User Manual

Chapter 4: Module Data, Status, and Configuration 41
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Enabled
0
Disabled 1
60 Hz
000
50 Hz 0 0 1
10 Hz 0 1 0
250 Hz 0 1 1
500 Hz 1 0 0
1 kHz 1 0 1
Upscale
00
Downscale 0 1
Last State 1 0
Zero 1 1
4 to 20 mA
00000
0 to 20 mA 00001
-10 to 10 V 00010
0 to 10 V 00011
1 to 5 V 00100
0 to 5 V 00101
+/-100 mV 00110
+/-50 mV 00111
Type J TC 01000
Type K TC 01001
Type T TC 0 1 0 1 0
Type E TC 01011
Type R TC 01100
Type S TC 01101
Type B TC 01110
Type N TC 01111
Type C TC 10000
100 Pt 385 1 0 0 0 1
200 Pt 385 1 0 0 1 0
500 Pt 385 1 0 0 1 1
1000 Pt 385 1 0 1 0 0
100 Pt 3916 1 0 1 0 1
200 Pt 3916 1 0 1 1 0
500 Pt 3916 1 0 1 1 1
1000 Pt 3916 1 1 0 0 0
10 Cu 426 1 1 0 0 1
120 Ni 618 1 1 0 1 0
120 Ni 672 1 1 0 1 1
604 NiFe 518 1 1 1 0 0
150 ohm 11101
1000 ohm 1 1 1 1 0
3000 ohm 1 1 1 1 1
Engineering Units X1
000
Engineering Units X10 0 0 1
Raw/Proportional 0 1 0
Scaled for PID 0 1 1
Percent range 1 0 0
Enable
0
Disable 1
Disable
0
Enable 1
Data Format
Cyclic Lead Comp.
2/4 Wire RTD
Make these bit settings
Open Circuit
Filter Frequency
Channel Disable
To Sel ec t
Input Type
NOTE Default settings for a particular function are indicated by zero(s).