In order to configure an I/O module, you must open up the configuration
tag for that module by clicking on the plus sign to the left of the
configuration tag in the Controller Tag data base.
Configuring aConfiguring a
Configuring aConfiguring a
Configuring a
1769sc-IF8U1769sc-IF8U
1769sc-IF8U1769sc-IF8U
1769sc-IF8U
UniversalUniversal
UniversalUniversal
Universal
ModuleModule
ModuleModule
Module
To configure the 1769sc-IF8U module in slot 1, click on the plus sign left
of Local:1:C. Configuration data is entered under the Local:1:C.Data tag.
Click the plus sign to the left of Local:1:C.Data to reveal the 10 integer
data words where configuration data may be entered for the 1769sc-IF8U
module. The tag addresses for these 18 words are Local:1:C.Data[0]
through Local:1:C.Data[17].
The first two configuration words are used to configure module functions
like CJC enable, cyclic calibration, open circuit detection and temperature
units (i.e. Celcious, Fahrenheit). Words 2 through 9 are used to configure
channels 0 through 7 respectively. All 8 words configure the same
parameters for the 8 different channels. For a complete description of
each of these parameters and the choices available for each of them, see
Configuration Data File in chapter 4.