User Manual

Compact IO™ Isolated HART Analog Input Module
U ser 's M a n u a l 0 300 21 5- 03 R ev. A
4-4
4. This screen is used to narrow your search for I/O modules to configure into your
system. Wit h the initial release of the CompactLogix5320 controller, this screen
only includes the “Generic 1769 Module”. Click the OK button and the
following default Generic Profile screen appears:
Figure 4-5
5. First, select the Com m Format (“Data – INT” for the 17 69sc-IF4IH) , then fill in
the name field. For this exa mple, “IF4IH” is used to help identif y the module
type in the Controller Or ganiz e r . T he Descrip tion field is optio nal and may be
used to provide more details co ncerni ng this I/O mod ule i n your application.
The slot number must be selected next, although it will begin with the first
available slot number, 1, and increments automatically for each subsequent
Generic Profile you configure. For this example, the 1769sc-IF4IH HART
module is located in slot 1.
The Comm Format, Assembly Instance and Size values are listed in the
following table for the 1769sc-IF4IH HART module:
Table 4-1 (Generic Profile Parameters)
1769 I/O
Module
Comm
Format
Parameter
Assembly
Instance
Size
(16-Bit)
IF4IH Data-INT Input
Output
Config
101
100
102
72
46
34
6. Enter the Assembly Instance numbers and their associated sizes for the 1769sc-
IF4IH module into the Generic Profile. When complete, the Generic Profile for a
1769sc-IF4IH module should look like the following: