User Manual

Compact IO™ Isolated HART Analog Input Module
U ser 's M a n u a l 0 300 21 5- 03 R ev. A
3-6
Panel Mount ing Using the Dimensional Template
Figure 3-4
Panel Mo unt ing Procedure Using Mo dules as a Template
The following procedure allo ws you to use the assembled modules as a te mplate for
drilling holes in the panel. If you have so p his ticated panel mounting equip ment, you can
use the dimensional template provided on the previous page. Due to module mounti ng
hole tolerance, it is important to follow these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all module-
mount ing holes on the panel.
3. Return the assembled modules to the clean work surface, including any previously
mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
NOTE If mounting more modules, mount only the last one of this group and put the
others aside. This reduces remounting time during d rilling and tapping of the next
group.
7. Repeat steps 1 to 6 for any remaining modules.
3.5.3 DIN Rail Mounting
The module can be mounted using the following DIN rails:
35 x 7.5 mm (EN 50 022 - 35 x 7.5), or
35 x 15 mm (EN 50 022 - 35 x 15).