User Manual

Compact IO™ Isolated HART Analog Input Module
U ser 's M a n u a l 0 300 21 5- 03 R ev. A
3-4
Sec t ion 3.4
System Assembly
The module can be attached to the controller or an adjacent I/O module before or after
mounting. For mounting instruction s, see Panel Mounting Usin g the Dimensional
Template, or DIN Rail Mounting. To work with a system that is alread y mounted, see
Replacing a Single Module within a System.
The following procedure shows you how to assemble the Compact I/O system.
Figure 3-2
1. Disconnect power.
2. Check that the bus le ver of the module to be installed is in the unlocked (fully right)
position.
NOTE: If the m odule is being installed to the left of an existing module, check that the
right-side adjacent module’s b us lever is i n the unlocked (fully right) position.
3. Use the upper and lower tongue-and-groove slots (1) to secure the modules together
(or to a controller).
4. Move the module back along the tongue-a nd- gro ove slots until the bus connector s
(2) line up wit h each other.
5. Push the bus lever back slig htl y to clear the positioning tab (3) . Use your finger s or a
small screwdriver.
6. To allow communication between the controller and module, move the bus lever
fully to the left (4) until it clicks. Ensure it is locked firmly in place.
!
Attention
When attaching I/O modules, it is very important that the bus
connectors are securely locked together to ensure proper electrical
connection.
7. Attach an end cap terminator (5) to the last module in the system by using the
tongue-and-groove slots as before.
8. Lock the end cap bus terminator (6).
!
Attention
A 1769-ECR or 1769-ECL right or left end cap respectively must be
used to terminate the end of the bus.