Environmental
Specifications
Shock & Vibrati on (o p) Class III
Shock Unpackaged (op) Class III, Cat. I
Operating Temperature 0 to 60 Degree C
1
Storage Temperature -40 to 85 Degree C
Humidity/Pressure 5 to 95% RH (non cond.)
Regulatory
Compliance
UL 508
ANSI/ISA 12.12.01
UL-C Class 1, Div2 Group A, B, C, D (CSA Equiv.)
CE compliance to EN 61010 -1 and EN 61131-2, EN55011, EN50082-2, and
EN61000-6-2
EN60079-0, EN60079-15 ATEX
Conditions of safe use:
Provision shall be made to prevent the rated voltage being exceede d by the
transient distur bances of more than 140% of t he peak rate d vol t age.
The system shall be mounted in an ATEX certified enclosure with a minimum
ingress protection rating of at least IP54 as defined in EN60529 and used in an
environment of not more than pollution degree 2.
The enclosure mu st have a door or cover accessible only by the use of a tool.
1
Avoid installing the module adjacent to modules with heat dissipation greater than 4 Watts when the ambient
temperature is in excess of 55°C. See Section 3. 3. 4 Sel ect i ng a Locat i o n, for more details.
0C < Ta < 60C
DEMKO 11 ATEX 1103437X
Ex n
A
IIC T4 Gc
II 3G