User Manual

Compact IO™ Isolated HART Analog Output Module
User’s Manual 03 00217-03 Rev. A
9-4
Table 9-3 (Module Error Types)
Err or Type Module Error
Fi e l d V a lu e Bi t s
11 through 9
(b in ar y)
Description
No err ors 000 No er r or is present. The extended error field holds no
additional information .
Hardw are
Errors
001 General and spec ific hardw are er r or codes ar e
specified in the extended error information field.
Configur ation
Errors
010 Module- specific error codes are indicated in the
extende d error f ield. Thes e err o r codes correspond to
options that you can change dir ectly. For example, the
input r ange or in put f ilte r s election.
9.6.2 Extended Error Information Field
Check the extended error information field when a non-zero value is present in the
module error field. Depending upon the value in the module error field, the extended
error information field can contain error codes that are module-specific or common to all
1769 analog modules.
Note: If no errors are present in the module error field, the ex tended error
information field is set to zero.
Hardware Errors
General or module-specific hardware errors are indicated by module error code 001. See
Table 9-4 (Extende d Faul t C o des) .
Configuration Errors
If you set the fields in the configuration file to invalid or unsupported values, the module
generates a critical error.
Table 9-4 (Extended Fault Codes) lists the possible module-specific configuration error
codes defined f or the mod ul e.