Instruction Manual

MicroLogix™ Combo Analog Input/Output Module 14
Publication 0100161-01 Rev. B
This table describes the channel specific configuration registers that are individually
selectable for output channels 0 through 3.
To Select
Make these bit settings
7 6 543210
Output Type
4 to 20 mA
000
0 to 20 mA
001
-10 to 10 V
010
0 to 10 V
011
1 to 5 V
100
0 to 5 V
101
Reserved
110
Channel Disabled
111
Data Format
Scaled for PID
00
Engineering Units
01
Percent Range
10
Raw/Proportional Data
11
Unused
0 0 0
This section details the channel specific configuration registers that are individually
selectable for channels 4 and 5
To Select
Make these bit settings
7 6 543210
Filter
Frequency
(Ignored if
Display CJC)
17 Hz 00
4 Hz 0 1
62 Hz 1 0
470 Hz 1 1
Data Format
Engineering Units X1 00
Engineering Units X10 0 1
Raw/Proportional
Data
10
Scaled for PID 1 1
MicroLogix™ Combo Analog Input/Output Module 11
Publication 0100161-01 Rev. B
Wiring the Finger-Safe Terminal Block
Be careful when stripping wires. Wire fragments that fall into
a module could cause damage when power is applied. Once
wiring is complete, ensure the module is free of all metal
fragments.
When wiring the terminal block, keep the finger-safe cover in place.
1. Route the wire under the terminal pressure plate. You can use the stripped
end of the wire or a spade lug. The terminals will accept a 6.35 mm (0.25
in.) spade lug.
2. Tighten the terminal screw making sure the pressure plate secures the
wire. Recommended torque when tightening terminal screws is 0.904 Nm
(8 in-lbs).
3. After wiring is complete, remove the debris shield.
If you need to remove the finger-safe cover, insert a screw
driver into one of the square wiring holes and gently pry the
cover off. If you wire the terminal block with the finger-safe
cover removed, you will not be able to put it back on the
terminal block because the wires will be in the way