Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status 57
Table 6.1f
Tag Name Data Type Style Description
Of8h0Configuration.ModuleConfigBits.14
2
BOOL DEC Bits 14 and 15 determine how often
the pass-through command is
serviced by the module.
15,14 = 00 = pass-through serviced
once per two channels scanned
15,14 = 01 = pass-through serviced
once per module scan
15,14 = 1X = pass-through serviced
once per channel scan
Of8h0Configuration.ModuleConfigBits.15
2
BOOL DEC Bits 14 and 15 determine how often
the pass-through command is
serviced by the module.
15,14 = 00 = pass-through serviced
once per two channels scanned
15,14 = 01 = pass-through serviced
once per module scan
15,14 = 1X = pass-through serviced
once per channel scan
2
The configuration of bits 14 and 15 directly effect the update time of the HART data acquisition for the module, for
example if bit 15 is set, the HART update time for each channel w ill be doubled.
Input Input
Input Input
Input
TT
TT
T
aa
aa
a
gsgs
gsgs
gs
The following fault and status reporting and module data sections allow
monitoring of faults, status, and input data from the module. These tags
can be found within the Of8h0Input controller tag.