Instruction Manual

40 ControlLogix
Analog HART Modules
Table 5.1c
Tag Name Data Type Style Description
If8h0Configuration.ChXHighHighAlarm
1
REAL FLOAT The high high process alarm trigger
point. Enter the value in terms of
engineering units.
If8h0Configuration.ChXAlarmDeadband
1
REAL FLOAT Forms a deadband around the process
alarms which causes the
corresponding process alarm status
bit to remain set until the input moves
beyond the trigger point by greater
than the amount of the alarm
deadband.
If8h0Configuration.ChXCalBias
1
REAL FLOAT
Offset to add to channel analog value
If8h0Configuration.HandleTimeout INT DEC There is a handle timeout associated
with the final reply message. After the
module obtaines the requested
information from the HART device, it
will start the HandleTimeout timer
(duration defined by the
HandleTimeout tag). The replay
message will be kept in memory
during the HandleTimeout period.
After the timeout occurs or after the
message is retrieved by the pass-
through response query command, the
storage buffer will be discarded, and
another pass through message will be
serviced without being rejected.
HandleTimeout is in the range of 1 to
255 seconds.
If8h0Configuration.ModuleConfigBits INT BIN Module function settings
If8h0Configuration.ModuleConfigBits.0 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.1 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.2 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.3 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.4 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.5 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.6 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.7 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.8 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.9 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.10 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.11 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.12 BOOL DEC Reserved set to zero
If8h0Configuration.ModuleConfigBits.13 BOOL DEC Reserved set to zero
1
X represents the module channel number (0 to 7).