The following tags allow for custom configuration of the module. These
tags can be found within the controller scope under the tag name
If8h0Configuration.
Table 5.1a
Tag Name Data Type Style Description
If8h0Configuration If8hConfigurationBlock NA Module configuration
If8h0Configuration.ConfigRevision SINT DEC Controls multiple owner connections.
0 = Always connect, overwrite w/new
configuration.
1 = Only connect if configuration
matches existing configuration.
If8h0Configuration.AdcFilter SINT DEC 0 = 10Hz 4 = 250Hz
1 = 50Hz 5 = 1000Hz
2 = 60Hz 6 = 20Hz
3 = 100Hz 7 = 15Hz
If8h0Configuration.RTS INT DEC The time in milliseconds that updated
input data is to be sent from the
module to the controller.
18 to 10000 msec
If8h0Configuration.ChXConfigBits
1
SINT BIN Channel configuration settings
If8h0Configuration.ChXConfigBits.0
1
BOOL DEC Unused
Set to zero
If8h0Configuration.ChXConfigBits.1
1
BOOL DEC Unused
Set to zero
If8h0Configuration.ChXConfigBits.2
1
BOOL DEC Unused
Set to zero
If8h0Configuration.ChXConfigBits.3
1
BOOL DEC Unused
Set to zero
If8h0Configuration.ChXConfigBits.4
1
BOOL DEC Enables latching for the rate alarm.
Latching causes the rate alarm to
remain set until an unlatch service is
explicitly sent to the channel or
alarm.
0 = Rate alarm unlatched
1 = Rate alarm latched
If8h0Configuration.ChXConfigBits.5
1
BOOL DEC Enables latching for all four process
alarms: low, low low, high, high high.
Latching causes the process alarm to
remain set until an unlatch service is
explicitly sent to the channel or
alarm.
0 = Alarms unlatched
1 = Alarms latched
If8h0Configuration.ChXConfigBits.6
1
BOOL DEC Disable alarms
0 = Enabled
1 = Disabled
If8h0Configuration.ChXConfigBits.7
1
BOOL DEC Enable HART Communication
0 = Disabled
1 = Enabled
1