Manual
Chapter 5: Channel Configuration, Data, and Status 43
Channel Specific
Settings
The following settings allow you to configure individual channel
parameters. Each channel, 0 through 7, has these tags.
Channel On/Off:
.DisableChannel 0, 1 BOOL
0: Channel is enabled.
1: Channel is disabled.
You may decrease the module sampling time by disabling unused channels.
Input Range/Type
.RangeType 0-37 INT
You can select from a series of operational ranges for each channel on
your module. The range designates the minimum and maximum signals
that are detectable by the module. In the case of thermocouple or RTD
sensors the selected type dictates the linearization curve of the particular
sensor.
0 = -0.05 to 0.05V (-0.075 to 0.075V) 19 = RTD 1000Ω Ni 618
1 = -0.15 to 0.15V (-0.175 to 0.175V) 20 = RTD 120Ω Ni 672
2 = 0 to 5V (-0.5 to 5.5V) 21 = RTD 10Ω Cu 426
3 = 1 to 5V (0.5 to 5.5V) 22 = RTD 604Ω Ni-Fe 518
4 = 0 to 10V (-0.5 to 10.0V) 23 = Resistance 0 to 250Ω
5 = -10.0 to 10.0V 24 = Resistance 0 to 500Ω
6 = 0 to 20mA (0 to 21.5mA) 25 = Resistance 0 to 1000Ω
7 = 4 to 20mA (3.5 to 21.5mA) 26 = Resistance 0 to 2000Ω
8 = RTD 100Ω Pt 385 27 = Resistance 0 to 3000Ω
9 = RTD 200Ω Pt 385 28 = Resistance 0 to 4000Ω
10 = RTD 500Ω Pt 385 29 = TC Type J
11 = RTD 1000Ω Pt 385 30 = TC Type K
12 = RTD 100Ω Pt 3916 31 = TC Type T
13 = RTD 200Ω Pt 3916 32 = TC Type E
14 = RTD 500Ω Pt 3916 33 = TC Type R
15 = RTD 1000Ω Pt 3916 34 = TC Type S
16 = RTD 120Ω Ni 618 35 = TC Type B
17 = RTD 200Ω Ni 618 36 = TC Type N
18 = RTD 500Ω Ni 618 37 = TC Type C