Chapter 2: Installing And Wiring Your Module 19
RTD Type Current Source V/
°
C
100Ω Pt 385 1.008mA 357µV/
°
C
200Ω Pt 385 1.008mA 714µV/
°
C
500Ω Pt 385 252µA 447µV/
°
C
1000Ω Pt 385 252µA 893µV/
°
C
100Ω Pt 3916 1.008mA 377µV/
°
C
200Ω Pt 3916 1.008mA 754µV/
°
C
500Ω Pt 3916 252µA 472µV/
°
C
1000Ω Pt 3916 252µA 941µV/
°
C
120Ω Ni 618 1.008mA 694µV/
°
C
200Ω Ni 618 1.008mA 1389µV/
°
C
500Ω Ni 618 252µA 867µV/
°
C
1000Ω Ni 618 252µA 1733µV/
°
C
10Ω Cu 426 252µA 9.7µV/
°
C
120Ω Ni 672 1.008mA 929µV/
°
C
The accuracies specified for the IF8u RTDs do not include errors due to
lead resistance imbalances.
Important: To ensure temperature or resistance value accuracy, the
resistance difference of the cable lead wires must be equal to or less than
0.01 ohms.
Important: Keep total lead resistance as small as possible and less than
25 ohms.
There are several ways to insure that the lead values match as closely as
possible. They are as follows:
* Use quality cable that has a small tolerance impedance rating.
* Use a heavy gauge lead wire which has less resistance per foot.