Instruction Manual

82 SLC 500
™
Universal Analog Input Module
Thermocouple C Type, Example Variations
-0.5
-0.4
-0.3
-0.2
-0.1
0
0.1
0.2
0.3
0.4
0.5
0 463 926 1389 1852 2315
Degrees C TC Input
Degrees C Variation
Ch 2 Delta, 25C
Ch 2 Delta, 0C
CH 2 Delta, 60C
RTD and Resistance
The following table provides the maximum error for each RTD and
resistance type when the 10 Hz, 50 Hz, and 60 Hz filters are used and the
module is operating at 25°C and was calibrated at 25°C. Errors due to
lead wire resistance mismatches are not included.
Input Max. Error
Type 25°C
100Ω Pt 385 ±1.0°C
200Ω Pt 385 ±0.7°C
500Ω Pt 385 ±0.6°C
1000Ω Pt 385 ±0.5°C
100Ω Pt 3916 ±0.9°C
200Ω Pt 3916 ±0.6°C
500Ω Pt 3916 ±0.5°C
1000Ω Pt 3916 ±0.4°C
10Ω Cu 426 ±3.0°C
120Ω Ni 618 ±0.4°C
120Ω Ni 672 ±0.4°C
3000Ω Resistance ±2.0 Ω