Instruction Manual

82 SLC 500
Universal Analog Input Module
Thermocouple C Type, Example Variations
-0.5
-0.4
-0.3
-0.2
-0.1
0
0.1
0.2
0.3
0.4
0.5
0 463 926 1389 1852 2315
Degrees C TC Input
Degrees C Variation
Ch 2 Delta, 25C
Ch 2 Delta, 0C
CH 2 Delta, 60C
RTD and Resistance
The following table provides the maximum error for each RTD and
resistance type when the 10 Hz, 50 Hz, and 60 Hz filters are used and the
module is operating at 25°C and was calibrated at 25°C. Errors due to
lead wire resistance mismatches are not included.
Input Max. Error
Type 25°C
100 Pt 385 ±1.0°C
200 Pt 385 ±0.7°C
500 Pt 385 ±0.6°C
1000 Pt 385 ±0.5°C
100 Pt 3916 ±0.9°C
200 Pt 3916 ±0.6°C
500 Pt 3916 ±0.5°C
1000 Pt 3916 ±0.4°C
10 Cu 426 ±3.0°C
120 Ni 618 ±0.4°C
120 Ni 672 ±0.4°C
3000 Resistance ±2.0