Instruction Manual

Chapter 4: Channel Configuration, Data, and Status 47
Channel 7:4 15 14 13 12 11 10 9 8 7 6 5 4 3210
Channel Channel disabled 0
Status Channel enable 1
4 to 20 mA 0 0 0 0 0
0 to 20 mA 0 0 0 0 1
± 0.05 V 0001 0
± 0.10 V 0001 1
± 0.50 V 0010 0
± 2.0 V 0010 1
0 to 5 V 0011 0
Input 1 to 5 V 0011 1
Type 0 to 10 V 0 1 0 0 0
±10V 0100 1
Thermocouple Type J 0 1 0 1 0
Thermocouple Type K 0 1 0 1 1
Thermocouple Type T 0 1 1 0 0
Thermocouple Type E 0 1 1 0 1
Thermocouple Type R 0 1 1 1 0
Thermocouple Type S 0 1 1 1 1
Thermocouple Type B 1 0 0 0 0
Thermocouple Type N 1 0 0 0 1
RTD 100
Ω
385 1 0 0 1 0
RTD 200
Ω
Pt 385 1 0 0 1 1
RTD 500
Ω
Pt 385 1 0 1 0 0
RTD 1000
Ω
Pt 385 1 0 1 0 1
RTD 100
Ω
Pt 3916 1 0 1 1 0
RTD 200
Ω
Pt 3916 1 0 1 1 1
RTD 500
Ω
Pt 3916 1 1 0 0 0
RTD 1000
Ω
Pt 3916 1 1 0 0 1
RTD 10
Ω
Cu 426 1 1 0 1 0
RTD 120
Ω
Ni 618 1 1 0 1 1
RTD 120
Ω
Ni 672 1 1 1 0 0
Resistance 3000
Ω
1110 1
Thermocouple Type C 1 1 1 1 0
CJC temperature 1 1 1 1 1
Engineering Units x1 0 0
Data Engineering Units x10 0 1
Format Scaled for PID 1 0
Proportional counts 1 1
Zero on open circuit 0 0
Open Max. on open circuit 0 1
Circuit Min. on open circuit 1 0
Disabled 1 1
Channel 10 Hz input filter 0 0
filter 50 Hz input filter 0 1
freq. 60 Hz input filter 1 0
250 Hz input filter 1 1
Open circuit No error 0
Open circuit detected 1
Under range No error 0
error Under range condition 1
Over range No error 0
error Over range condition 1
Channel No error 0
error Channel error 1