Instruction Manual

Chapter 4: Channel Configuration, Data, and Status 41
Table 4.3 1746sc-NI8u Universal Module -
Channel Data Word Format
Data Format
Input Engineering Units x 10 Engineering Units x 1 Proportional
Type ° Celsius ° Fahrenheit ° Celsius ° Fahrenheit Scaled-for-PID Counts
4-20 mA * +400 to +2,000 +4,000 to +20,000 0 to 16,383 -32,768 to 32,767
0-20 mA * 0 to +2,000 +0 to +20,000 0 to 16,383 -32,768 to 32,767
± 0.05 V * -500 to +500 -5,000 to +5,000 0 to 16,383 -32,768 to 32,767
± 0.10 V * -1,000 to +1,000 -10,000 to +10,000 0 to 16,383 -32,768 to 32,767
± 0.50 V * -5,000 to +5,000 N/A 0 to 16383 -32,768 to 32,767
± 2.0 V * -2,000 to +2,000 -20,000 to +20,000 0 to 16,383 -32,768 to 32,767
0-5 V * 0 to +5,000 N/A 0 to 16,383 -32,768 to 32,767
1-5 V * +1,000 to +5,000 N/A 0 to 16,383 -32,768 to 32,767
0-10 V * 0 to +10,000 N/A 0 to 16,383 -32,768 to 32,767
±10 V * -10,000 to +10,000 N/A 0 to 16,383 -32,768 to 32,767
J -210 to 760 -346 to 1,400 -2,100 to 7,600 -3,460 to 14,000 0 to 16,383 -32,768 to 32,767
K -270 to 1,370 -454 to 2,498 -2,700 to 13,700 -4,540 to 24,980 0 to 16,383 -32,768 to 32,767
T -270 to 400 -454 to 752 -2,700 to 4,000 -4,540 to 7,520 0 to 16,383 -32,768 to 32,767
E -270 to 1,000 -454 to 1,832 -2,700 to 10,000 -4,540 to 18,320 0 to 16,383 -32,768 to 32,767
R 0 to 1,768 32 to 3,214 0 to 17,680 320 to 32,140 0 to 16,383 -32,768 to 32,767
S 0 to 1,768 32 to 3,214 0 to 17,680 320 to 32,140 0 to 16,383 -32,768 to 32,767
B 300 to 1,820 572 to 3,308 3,000 to 18,200 5,720 to 32,767** 0 to 16,383 -32,768 to 32,767
N 0 to 1,300 32 to 2,372 0 to 13,000 320 to 23,720 0 to 16,383 -32,768 to 32,767
C 0 to 2315 32 to 4199 0 to 23,150 32 to 32767** 0 to 16,383 -32, 768 to 32-767
10
Ω
Cu 426 -100 to 260 -148 to 500 -1,000 to 2,600 -1,480 to 5,000 0 to 16,383 -32, 768 to 32-767
120
Ω
Ni 618 -100 to 260 -148 to 500 -1,000 to 2,600 -1,480 to 5,000 0 to 16,383 -32, 768 to 32-767
120
Ω
Ni 672 -80 to 260 -112 to 500 -800 to 2,600 -1,120 to 5,000 0 to 16,383 -32, 768 to 32-767
3000
Ω
* 0 to 3,000 0 to 30,000 0 to 16,383 -32, 768 to 32-767
100
Ω
Pt 385 -200 to 850 -328 to 1,562 -2,000 to 8,500 -3,280 to 15,620 0 to 16,383 -32,768 to 32,767
200
Ω
Pt 385 -200 to 750 -328 to 1,382 -2,000 to 7,500 -3,280 to 13,820 0 to 16,383 -32,768 to 32,767
500
Ω
Pt 385 -200 to 850 -328 to 1,562 -2,000 to 8,500 -3,280 to 15,620 0 to 16,383 -32,768 to 32,767
1,000
Ω
Pt 385 -200 to 850 -328 to 1,562 -2,000 to 8,500 -3,280 to 15,620 0 to 16,383 -32,768 to 32,767
100
Ω
Pt 3916 -200 to 630 -328 to 1,166 -2,000 to 6,300 -3,280 to 11,660 0 to 16,383 -32,768 to 32,767
200
Ω
Pt 3916 -200 to 630 -328 to 1,166 -2,000 to 6,300 -3,280 to 11,660 0 to 16,383 -32,768 to 32,767
500
Ω
Pt 3916 -200 to 630 -328 to 1,166 -2,000 to 6,300 -3,280 to 11,660 0 to 16,383 -32,768 to 32,767
1,000
Ω
Pt 3916 -200 to 630 -328 to 1,166 -2,000 to 6,300 -3,280 to 1,1660 0 to 16,383 -32,768 to 32,767
C J C -25 to 105 -13 to 221 -250 to 1,050 -130 to 2,210 0 to 16,383 -32,768 to 32,767
* When current, voltage, or resistance input types are selected, the temperature setting is ignored and does not affect the data format.
** When Type B or Type C thermocouples cannot be represented in engineering units x 1 in °F above 3276.6°F, the module’s software will treat it as an
over range condition if that channel has input to full scale.