Owner's manual
2-8  Chapter 2: Installation and Wiring 
User’s Manual Pub. 0300272-01 Rev. A.0 
Section 2.5 
Field Wiring 
Connections 
Consider the following when wiring your system: 
General 
  Power and input wiring must be in accordance with Class 1, Division 2 
wiring methods, Article 501-4(b) of the National Electric Code, NFPA 70, 
and in accordance with the authority having jurisdiction. 
  Use Belden™ 8761 or equivalent, shielded wire. 
  To ensure optimum accuracy, limit overall cable impedance by keeping a 
cable as short as possible. Locate the module as close to input devices as the 
application permits. 
  Digital and analog power must be supplied by an Isolated Secondary 
Limited Energy Low Voltage source. 
Outputs 
  The module provides loop power for analog outputs. 
Grounding 
NOTE 
Use supply wires suitable for 10°C above surrounding ambient 
temperature. 
  This product is intended to be mounted to a well-grounded mounting 
surface such as a metal panel. Additional grounding connections from the 
module’s mounting tabs or DIN rail (if used) are not required unless the 
mounting surface cannot be grounded. 
  Under normal conditions, the drain wire (shield) should be connected to the 
metal mounting panel (earth ground). Keep shield connection to earth 
ground as short as possible. 
  Ground the shield drain wire at one end only. The typical location is as 
follows: 
-  For grounded thermocouples or millivolt sensors, this is at the 
sensor end. 
-  For insulated/ungrounded thermocouples, this is at the module end. 
Contact your sensor manufacturer for additional details. 
Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-
Bradley publication 1770-4.1, for additional information. 










