User Manual

3-16 Point IO™ 4 Channel Universal Analog Input Module
User’s Manual Pub. 0300266-01 Rev. A
2/3/4 Wire RTD (Bits 13 and 14)
ThesebitsareusedforRTDandResistancemodesonly.Theyareusedtospecify
2,3,or4wireRTDmodes.Thissettingisignoredfornonresistance/RTDinput
types.Defaultsettingis3wire.
Temperature Scale (Bit 15)
Setto1todisplaydegreesFahrenheit.Otherwise0displaystemperaturein
degreesCelsius(default).Thisfieldshallbeignoredfornontemperatureranges.
Section 3.6
Read Input
Data
The input data file contains module status information and analog input data for each of
the input channels. Analog input data is read for each channel, converted to a scaled
digital value, and stored in the input tags. The input tags for the IF4U are located under
the controller tags. The following examples describe the tag structure allocated by the
Generic Module profile and the AOP.
Generic Module Profile:
[Name of remote communication module]:e:x.Data[0 to 198]
e = IF4U slot number
x = Image Type (i.e. C, I, or O)
AOP (Add-On-Profile):
[Name of remote communication module]:e:x
e = IF4U slot number
x = Image Type (i.e. C, I, or O)
Note: The AOP will provide a predefined tag structure for the input tags.
See example below.
Figure 7 (AOP Input Tags)