The modules flow meter mode is compatible with a variable reluctance AC input, which counts AC zero crossing
signals from 50 mV to 75V AC peak.
Count input modes include uni-directional, bi-directional and quadrature. Bi-directional and quadrature inputs
require the use of two inputs, with up to four counters of this type being supported.
The module accepts +5 to +45 V gating (enable) pulses for standard meter proving applications. To
accommodate these pulses, the module uses a pulse-to-enable converter circuit that can be enabled and disabled
with software. Note that this module does not perform pulse interpolation for meter proving.
The module also has external inhibit/trigger lines using a 5V discrete pulse to regulate activity.
Module Features
The Quantum counter module features:
• Eight input channels
• Support for four quadrature encoders
• Eight external enable inputs
• Input voltage ranges: AC (50 mV to 75V peak), 5VDC, 12VDC, 24VDC
• Eight 24V gating (enable) pulses for meter proving
• Input filter frequency 50 kHz max., AC or DC
• Maximum count value 65 K or 16 M
• Programmable scaling, K, M, and R factors
• Channel update time 4 ms/channel
• Rate output
• Counter logic level state
• Programmable counter functions: start, stop, reset, preset, max limit
• Programmable counter alarm flags and zero flags in internal counter and rate operating modes
• Two software-selectable filters: 30 or 50 kHz digital, 15 kHz analog
• Channel-to-backplane isolation 1000VDC
• Channel-to-channel isolation 0 V