Owner's manual
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc
76
AAppendix
Specifications
This appendix lists the specifications for the Quantum counter module.
Specification Value
Data Registers 8 - 3X registers 10 - 4X registers 8 - zoom (parameter) registers
LED Indicators:
1 Green LED, Module Status The module status LED indicates the status of the power-up self-test. The LED is on
when the module is ready. Any self-test error is indicated with a blink code.
8 Green LEDs, Channel Status Each channel status LED indicates that the
corresponding channel is active.
Terminal Block 40-pin removable connector
Wire Size One 14 AWG wire or two 22 AWG wires
Backplane Interface Standard ASIC and dual port memory interface
Compatibility:
Hardware All Quantum PLC racks
SoftwareModSoft, Concept, and ProWorks
Dimensions Standard slot configuration (using a standard single-slot plastic case, and existing
shipping box)
Shipping Weight 300 g (.65 lb)
Environmental Specifications
Environmental testing is in accordance with the standards specified or in accordance with Schneider Alliance
IPA2000/3000 or equivalent. For reference see SA IAP 2000, Mechanical Environmental Specifications #043
500021, revision 1.02.
Test Description Standard Class/Limit
Mechanical:
Vibration of Unpackaged Products IEC 68-2-6 5g at 10-500 Hz per product
Shock of Unpackaged Products Operating 15 g peak acceleration, 11±1 ms pulse width
Non-operating 50 g peak acceleration, 11±1 ms peak width
Temperature/Humidity:
Operating Temperature 0 to 60°C (32 to 131 °F), min.
Storage Temperature -40 to 85 °C (-40 to 185°F)
Humidity-Temperature IEC 68-2-3 0 to 95 percent RH noncondensing at 60 °C
Altitude 2000 meters fully operational
Electrical:
Electrostatic Discharge IEC 801-2
Surge Transient Susceptibility
Radiated EMI Susceptibility IEC 801-3
Dielectric Withstand
Conducted EMI Susceptibility
Conducted Emissions CISPR 11 Class A