Owner's manual

Counter / Flow Meter Input Module
65
Corrective Action
If necessary, install a pull-down resistor between the channel input and channel common or a pull-up resistor
to a positive voltage source.
Module Not Recognized by Rack (ModSoft)
Possible Causes
Module not correctly installed.
Module runtime files not correctly installed.
Corrective Action
1. Reinstall the module in the rack. See chapter 2, Installation and Wiring.
2. Check the I/O map screen in ModSoft to see if the problem still exists.
3. If the module name is still marked with an asterisk (indicating a health status problem), select the
module name using the Shift+? key.
4. If the module is not listed at all, reinstall the ModSoft runtime files. See software installation
instructions in chapter 3, Module Configuration.