Owner's manual
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc
40
Bit Settings for 3X+0 Registers
The 3X+0 registers contain data, scaling and status information for channels 1 through 8. You
can only set 3X register bits using ladder logic. This section describes the layout for the registers
and defines the bits. Ladder logic examples are provided in chapter 4, “Programming.”
Table 3-7 3X+0 Register Bit Settings
Function 1 2 3 45678910111213141516
Bank/Data FormatBank 1/ LSW 00
Select Echo Bank 2/ MSW 01
Bank 3/Rate 10
Bank 4/ Status 1 1
Data Delivery EchoComprehensive 0
Speed 1
Multiplexing Manual 0
Control Echo Autosequence 1
Parameter Definition Preset 0 0 0
Echo Count Limit 0 0 1
(for scale/limit word) Rate Limit 0 1 0
M factor 0 1 1
K Factor 1 0 0
R factor 1 0 1
Not Used X
Channel Number Channel 1 0 0 0
Echo Channel 2 0 0 1
(for scale/limit word) Channel 3 0 1 0
Channel 4 0 1 1
Channel 5* 1 0 0
Channel 6* 1 0 1
Channel 7* 1 1 0
Channel 8* 1 1 1
Not Used X
Configuration ErrorNo Error 0
Error 1
System Error No Error 0
Error 1
Program Do Not Program0
EEPROM Echo Program 1
Enable Scale Disable 0
/Limit Word Enable 1
Echo
All fields in the above table are echoes of what is in the 4X+0 register except configuration error and system error. Refer
to the section Configuration Word (4X+0 Register) for more details. Configuration error indicates an erroneous configu-
ration has been input for at least one input channel. A system error indicates a problem with either the module or with a
module input.