Counter / Flow Meter Input Module Cat. No. Quantum Automation Series 140 EHC 204 00sc - 4 Channel 140 EHC 208 00sc - 8 Channel Installation Instructions Owners Guide 0300185-01 Rev.
Counter / Flow Meter Input Module Contents What this Guide Covers ....................................................................................................................................................... 6 Who Should Use This Guide ................................................................................................................................................ 6 Manual Contents ......................................................................................................
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Making Bit Settings for Zoom Registers ............................................................................................................................ Zoom Register Layout ................................................................................................................................................... Input Range, Bits 15 and 16 ...................................................................................................
Counter / Flow Meter Input Module K & M Factor Set Flag: Bit 3 ........................................................................................................................................ 44 R Factor Set Flag: Bit 2 ................................................................................................................................................. 44 Configuration Error Flag: Bit 1 .......................................................................................................
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Preface Read this preface to familiarize yourself with the rest of the manual. This preface covers the following topics: • What this guide covers • Who should use this guide • Contents of the guide • Related publications • Conventions used in this guide What this Guide Covers This guide describes the hardware and firmware included in the 4- and 8-channel Quantum™ Counter/Flow Meter modules for the Schneider Automation Series Quantum PLC.
Counter / Flow Meter Input Module Related Documentation The table below lists a number of reference documents that provide information to assist you when working with one of the Quantum counter modules.
Quantum Series 8 140 EHC 204 00sc 140 EHC 208 00sc
Counter / Flow Meter Input Module 1Chapter Overview This chapter describes the 4- or 8-channel Quantum Counter/Flow Meter input module (called Quantum counter module in this document). It also explains how the Schneider Automation Series Quantum PLC reads input data from a Quantum counter module. Shipped with your module is an MS-DOS formatted floppy disk titled Quantum Runtime Files, Spectrum Controls, Inc. The disk contains runtime files that are required to use all versions of this module.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc The modules flow meter mode is compatible with a variable reluctance AC input, which counts AC zero crossing signals from 50 mV to 75V AC peak. Count input modes include uni-directional, bi-directional and quadrature. Bi-directional and quadrature inputs require the use of two inputs, with up to four counters of this type being supported. The module accepts +5 to +45 V gating (enable) pulses for standard meter proving applications.
Counter / Flow Meter Input Module Hardware Features The Quantum counter module contains a removable Modicon 40-pin terminal block providing connections for up to eight input devices. The illustration below shows the hardware features of the module. For quadrature operation, the module configures channels into quadrature encoding pairs. Both channels in a pair must be configured for quadrature mode. Quadrature encoding reports the same quadrature count value on the output of each channel.
Quantum Series 140 EHC 204 00sc Hardware Door (removable) Door label LED indicators 140 EHC 208 00sc Description Covers the terminal block and includes an identification label for terminals. Permits easy terminal identification. Display operating and fault status of module. Details are provided in “Diagnostic LEDs”. Provides module identification. Secure module in rack slot. Used for field wiring the module.
Counter / Flow Meter Input Module Table 1-3 Blink Codes for Fault LED Code (Number of Blinks) Off 1 2 3 4 5 6 7 8 9 10 Error Type No Faults Dual Port RAM fault. FPGA init fault. FPGA1 program fault. FPGA2 program fault. FPGA1 fault. FPGA2 Fault. Watchdog Fault. ROM CRC fault. EEPROM fault. Both Speed mode and Autosequence mode selected (Mutually exclusive) Recommended Cables To minimize interference from radiated electrical noise, we recommend twisted-pair and shielded cables.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc 2Chapter Installation and Wiring This chapter includes information about: • Module compliance with safety standards • Power requirements • Installation considerations, such as prevention of electrostatic discharge • Installing the module • Field wiring of the module and analog input devices Compliance with Safety Standards The module is compliant with the safety standards described in this section. It is intended for use in an industrial environment.
Counter / Flow Meter Input Module Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, since it operates with inputs under 75 VDC and 50VAC rms. It applies the safety requirements of EN 61131-2 Programmable Controllers, Part 2 Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication. Power Requirements The module receives power through the PLC backplane from the +5VDC power supply.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Reducing Noise Most applications require installation in an industrial enclosure to reduce the effects of electrical interference. Electrical noise, to which analog inputs and outputs are highly susceptible, will reduce the performance (accuracy) of the module. Selecting a Location WARNING EXPLOSION HAZARD This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or nonhazardous locations only.
Counter / Flow Meter Input Module • Routing field wiring in a grounded conduit can reduce electrical noise. • If field wiring must cross AC or power cables, ensure that they cross at right angles. • If multiple power supplies are used with analog inputs, the power supply commons must be connected. • To ensure optimal accuracy, limit overall cable impedance by keeping a cable as short as possible. Locate the module as close to input devices as the application permits. • Tighten terminal screws with care.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Inserting the Module in the PLC Rack Do the following to place the module in the PLC rack: 1. Ensure that the rack is properly grounded and installed in a NEMA-rated enclosure. 2. Disconnect all power to the module, and disconnect it from any connected devices. See Removing Power. WARNING Installation or removal of the module with power applied can cause an electrical arc.
Counter / Flow Meter Input Module Removing and Replacing the Terminal Block When wiring the module, it is not necessary to remove the terminal block. However, if necessary, you can use this procedure for removal and replacement. 1. Loosen the upper and lower retaining screws, alternating between screws. The terminal block backs away from the module as you remove the screws. 2. Carefully pry the terminal block loose. 3. When ready to replace the terminal block, insert and tighten the retaining screws.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Wiring the Terminal Block The module terminal block has eight shield terminals provided as frame ground connections for input wire shielding. It also provides eight external encoder disable pins used to externally gate each input. A low input allows each channel (or channel pair) to operate. There are also 8 counter enable lines that are compatible with 5, 12, and 24 VDC inputs.
Counter / Flow Meter Input Module Specification Wire Type Wire Size Terminal Screw Torque Retaining Screw Torque Value Stranded, Cu-90°C (194°F) 16 to 22 AWG 0.68 Nm (6 in-lb) 0.46 Nm (4.1 in-lb) To wire the terminal block: 1. Determine the length of cable you need to connect a channel to its field device. Remember to include additional cable to route the drain wire and foil shield to their ground points. 2.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc CAUTION - Be careful when stripping wires. Wire fragments that fall into a module could cause damage at startup. 3. At the module end of the cable, cut the drain wire and foil shield. 4. Check the signal wires to ensure that they are the correct length to connect to the terminal block. 5. At the input device end of the cable, twist the drain wire and foil shield together.
Counter / Flow Meter Input Module 3Chapter Module Configuration This chapter includes information on the following: • Module addressing • Setting up the PLC configuration software (ModSoft, Concept, and SCIOCFG) • Making bit settings for zoom (parameter) registers • Making bit settings for 4X configuration (output) registers • Making bit settings for 3X data and status registers Some configuration can be performed using the ModSoft, Concept, and SCIOCFG configuration programs.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Module Addressing The module uses sixteen zoom (parameter) registers, nine 4X (output) registers for configuration words, and eight 3X (input) registers for data and status words. Table 3-1 Module Registers Register Function Zoom+0..7 Basic Configuration data (4ch - 0..3 / 8ch - 0..
Counter / Flow Meter Input Module Setting Up the Configuration Software The module is compatible with several configuration software packages: ModSoft version 2.4 or later, Concept version 2.1 or later, and ProWorx NxT. Setup and configuration instructions for ModSoft and Concept are provided in this manual. Included with the module is a 3.5-inch floppy disk. Install the disk files to update the configuration software so that you can properly configure your module.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Setting Zoom Registers Using ModSoft The procedure below tells how to enable the zoom registers and make configuration settings in ModSoft. Refer to Zoom Register Layout. 1. Ensure that the ModSoft configuration software has been updated from the module installation disk, as described in “ Setting Up ModSoft” . 2. Open ModSoft, and access the I/O map screen. 3. Select the slot in which you have installed the module. 4.
Counter / Flow Meter Input Module Setting Zoom Registers Using Concept The next procedure describes how to enable the zoom registers and make configuration settings in Concept. Refer to Zoom Register Layout. 1. Ensure that the Concept software has been updated from the installation disk as described in “Setting Up Concept.” 2. Start the Concept Modconnect tool (Modconf.exe). 3. From Modconnect, open the file SPECTRUM.MDC. 4. Select the Quantum counter module, or click Add All. 5.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Setting Up SCIOCFG Software Version 2.1 of Concept introduced a tool for importing Modconnect module definition files into the Concept database. This allows you to configure Modconnect I/O. However, Concept 2.1 does not provide a means for you to design your own I/O configuration menus. Instead, Concept provides a generic interface in which you must enter configuration parameters in hexadecimal values.
Counter / Flow Meter Input Module Zoom Register Layout The following table shows the layout for each of the zoom registers. The 8 channel module uses this layout for the first eight registers. The four channel uses the first 4 zoom registers. (The nineth - 8 channel or 5th - channel zoom register specifies the Bank Switch Period in the Autosequence Mode.) , with bit 1 the MSB and bit 16 the LSB.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Uni-Directional With this configuration, the input increments in an upward direction. All 8 channels may be configured in the unidirectional mode. Every clock pulse will increment the counter on the rising edge. Note: The direction of the counter may be inverted by setting the Count Direction bit described in the Configuration chapter. Bi-Directional The bidirectional counter requires 2 input channels.
Counter / Flow Meter Input Module 30 kHz Filter, Bit 12 The 30 kHz filter is recommended for counter or flow meter applications running at speeds less than 25 kHz. Set this bit to 0 when running to speeds of 50 kHz. Setting this bit to 1 filters input noise above 30 kHz. 15 kHz Filter, Bit 11 The 15 kHz filter is recommended for counter or flow meter applications running at speeds less than 15 kHz. Set this bit to 0 when running to speeds above 15 kHz.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Making Bit Settings for 4X Registers You can only set 4X register bits using ladder logic. This section describes the layout for the registers and defines the bits. Ladder logic examples are provided in chapter 4, Programming. The first 4X register controls channel enabling and multiplexing. The following table shows the bit settings for this register.
Counter / Flow Meter Input Module Bank/Data Format Select: Bits 15-16 The function of these two bits is determined by the Data Delivery Mode, Bit 14. If the Data Delivery Mode is comprehensive, Bit 14 = 0, the bank will be displayed as shown below: 00: Bank 0 – channels 1 and 2 01: Bank 1 – channels 3 and 4 10: Bank 2 – channels 5 and 6 11: Bank 3 – channels 7 and 8 If the Data Delivery Mode is Speed, Bit 14 = 1, the bank will be displayed as shown below: 00: All channels Count LSW only.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Due to the limited register availability of the Quantum Platform, the scale and limit factors are multiplexed onto register 4X+1. Changing these values will generally occur either at power-up or line changeover. On power up, scale factors default to the values stored in EEPROM and the count limit values (preset, count limit, and rate limit) default to zero.
Counter / Flow Meter Input Module Counter Preset: This output data word is used in conjunction with the Counter Preset enable bit. When this bit is set, the value in the counter preset word is loaded into the counter. The counter preset can be used to set the counter to an initial starting value. The bit should be set for at least one I/O scan. The bit can be held on until the data in the counter data is verified to be equal to the preset value.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc R Rate Factor: The R scale factor can be used for scaling of the output frequency. The output frequency is divided by the R scale value. Typically a factor of two will be used. The result is the rate data value being 1/2 of the actual value. R factors must be positive numbers. Rate Output Value = Actual Rate Value / R Factor Layout for 4X+2 through 4X+9 Registers Registers 4X+2 through 4X+9 registers contain control word information for the each channel.
Counter / Flow Meter Input Module Preset, Bit 15 Set bit 15 to 1 to load the counter preset value into the counter. This value is used to set the counter to an initial starting value. Set bit 15 for at least one I/O scan, and hold it on until counter data is verified to be equal to the preset value. The counter holds the preset value until the bit 15 is turned off (set to 0). At this time normal counter functions resume. NOTE A counter preset function begins when bit 15 is set to 0.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc State, Bit 6”. Zero For the Counter Indicates when the count is zero. The status of the flag is reflected in the counter zero bit in the 3X state register register for the channel. See “ Counter Zero State, Bit 8”. For the Input Rate Indicates when the input rate is zero or below. The status of the flag is reflected in the rate zero bit in the 3X state register register for the channel. See “ Rate Zero State, Bit 5”.
Counter / Flow Meter Input Module Roll over to, Bit 7 When the counter exceeds the maximum count or limit value it will roll over the top. When the counter rolls over it can roll over to a starting value of zero, or it can start at the user-defined Preset value. When this bit is set to zero the counter will roll over to zero. When set to 1 the counter will roll over to the preset value. If the stop on limit flag is set the counter will not roll over until the flag is released.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Bit Settings for 3X+0 Registers The 3X+0 registers contain data, scaling and status information for channels 1 through 8. You can only set 3X register bits using ladder logic. This section describes the layout for the registers and defines the bits. Ladder logic examples are provided in chapter 4, “Programming.
Counter / Flow Meter Input Module The process for updating the scale coefficients and the count limits is as follows: 1. Set the Scale/Limit Word to its desired value (4x+1 register). This must be performed before updating the module control word. 2. Set the following bits on the module control word (register 4X+0) to the appropriate state for the value to be written: a. Channel Number b. Parameter Definition c.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc The 3X registers (3X+1 through 3X+8) contain data and status information for channels 1 through 8. You can only set 3X register bits using ladder logic. This section describes the layout for the status registers (3X+1 through 3X+8) and defines the bits. Ladder logic examples are provided in chapter 4, “Programming.
Counter / Flow Meter Input Module Counter Preset Flag: Bit 15 When the Counter Preset value is reached this flag bit is set. The bit is reset when the counter in incremented up or down from the Preset value. Gate Enable Echo: Bit 14 This bit echos the state of the gate enable line. The gate enable line is an external logic line used to time counter events. Counter Invert Echo: Bit 13 This bit echos the state of the counter direction. The invert flag indicates if the invert bit has been set.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Counter Limit Flag: Bit 8 This flag indicates that the counters accumulator has reached its user-defined count limit. When the Counter Limit word is in use, i.e. it has a value other than zero, then the Counter Range flag indicates the counter is at the User defined limit. When the counter value is equal to the Limit value the Counter Limit flag bit will be set until the Reset Flags Bit is set.
Counter / Flow Meter Input Module 45
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc 4Chapter Programming With configuration complete, it is time to prepare ladder logic to reflect your configuration settings. Programming the module requires knowledge of counter configuration, PLC ladder logic, and data management.
Counter / Flow Meter Input Module Address Description 300001 3x Register Counter card Configuration Word echo 300002 3x+1 Register Channel Data word 1 300003 3x+2 Register Channel Data word 2 300004 3x+3 Register Channel Data word 3 300005 3x+4 Register Channel Data word 4 300006 3x+5 Register Channel Data word 5 300007 3x+6 Register Channel Data word 6 300008 3x+7 Register Channel Data word 7 300009 3x+8 Register Channel Data word 8 400200 N/A Channel 1 Preset 40020
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Address Description 400800 N/A Channel 7 400801 N/A Channel 7 Count limit 400802 N/A Channel 7 Rate limit 400803 N/A Channel 7 M factor 400804 N/A Channel 7 K factor 400805 N/A Channel 7 R factor 400900 N/A Channel 8 Preset 400901 N/A Channel 8 Count limit 400902 N/A Channel 8 Rate limit 400903 N/A Channel 8 M factor 400904 N/A Channel 8 K factor 400905 N/A Channel 8 R factor 401100 N/A Channel 1 Count da
Counter / Flow Meter Input Module Example : Demultiplexing Data The following ladder logic shows how to move data from the 4 multiplexed input words to a block of 8 output words starting at location 400001 using the manual mode. This and other ladder logic samples may be found on our website, www.spectrumcontrols.com.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc General Programming Examples Example 1: Loading Scaling Factors The following sample ladder logic shows how to load scale factors into the module. Refer to the configuration bit table for information regarding factor and channel bit settings Initialization: First Pass Condition - Coil 1 is True for only one scan. Rung 3 starts and stops the ladder following this network.
Counter / Flow Meter Input Module Select Channel - Rungs 1 and 2 select and load the data for channels 1 and 2 respectively. Select Channel - Rungs 1 and 2 select and load the data for channels 3 and 4 respectively.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Select Channel: Rungs 1 and 2 select and load data for channels 5 and 6 respectively Select Channel: Rungs 1 and 2 select and load data for channels 7 and 8 respectively 52
Counter / Flow Meter Input Module Stop Ladder: Rung 1 stops the ladder after all the data has been loaded for channels 1-8 Select Variable: Rungs 1, 2 and 3 select one of the following variables: Preset, Count Limit, Rate Limit, M Factor, K Factor, and R Factor.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Select Variable: Rungs 1, 2 and 3 select one of the following variables: Preset, Count Limit, Rate Limit, M Factor, K Factor, and R Factor. Select the channel: When coil 3 is energized the counter is incremented, selecting the next channel. When the accumulated value of the counter reaches 8 the ladder stops executing.
Counter / Flow Meter Input Module Pass the variable to the counter card: Rung 1 loads the current variable (Preset, Count, Limit, Etc.) in to a temporary holding register. Rung 3 passes the value stored in the temporary holding register to the counter card.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Sample Configuration Simple Bi-Directional Ring Counter: The figure below demonstrates ring counter operation. In a ring counter operation, the count value changes between zero and maximum. If, when counting up, the counter reaches the maximum value, it rolls over to zero. If, when counting down, the counter reaches zero, it rolls under to the maximum value.
Counter / Flow Meter Input Module Sample Configuration Using the Meter Proving Inputs A ball proving system would use the meter proving input found on the module. The ball meaures the flow velocity over a fixed length of line. When the ball crosses the starting point a momentary high signal from a proximity switch starts the counter. When the ball crosses the prover exit another proximity switch triggers causing the counter to stop. During the movement of the displacer the meter count is monitored.
Quantum Series 58 140 EHC 204 00sc 140 EHC 208 00sc
Counter / Flow Meter Input Module 5Chapter Maintenance and Diagnostics This chapter describes maintenance and diagnostics for the Quantum counter module. Provided information includes: • Safety considerations during maintenance • Preventive maintenance • Internal diagnostics • Startup testing • Troubleshooting • Module errors Safety Considerations Safety considerations are an important element of proper maintenance and diagnostic procedures.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Standing Clear of the Equipment When troubleshooting any system problem, have all personnel remain clear of the equipment. The problem can be intermittent, and sudden unexpected machine motion can occur. Have someone ready to operate an emergency stop switch in case it is necessary to shut off power.
Counter / Flow Meter Input Module Internal Diagnostics The module performs internal diagnostics at both the module and channel levels of operation. When detected, module error conditions are immediately indicated by the ready (module status) LED. Channel errors are reported at their respective LEDs. The module reports error conditions to the PLC. Channel error conditions are reported in the module’s input data table. Module hardware errors are typically reported in the PLC I/O status file.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Startup Testing This section presents testing procedures recommended for use at module startup to verify correct installation and configuration. Physical Inspection 1. Inspect the module to ensure that all wire connections are correct and secure and that no wires are missing or broken. 2. Ensure that the shield for the cable used to wire your module is properly grounded. Refer to Chapter 2, “Installation and Wiring” for more information. 3.
Counter / Flow Meter Input Module Health Status Test (Concept) 1. In Concept, access the I/O configurator and ensure that the module description, slot location, and register assignments are correct. 2. Use the controller status to verify that the module is recognized and reported as healthy. If you find an asterisk in front of the module name, the rack does not recognize the module. To correct the problem, see troubleshooting. Register Operation Test 1.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc Active LED Does Not Illuminate Possible Causes The module is not communicating with the PLC rack. Corrective Action 1. Deinstall the module. See chapter 2, “Installation and Wiring.” 2. Place the rack in run mode. 3. Reinstall the module in the rack. See chapter 2, “Installation and Wiring.” Fault LED Does Not Illuminate Possible Causes • Module self-test error • Fatal hardware error Corrective Action Contact your local distributor.
Counter / Flow Meter Input Module Corrective Action If necessary, install a pull-down resistor between the channel input and channel common or a pull-up resistor to a positive voltage source. Module Not Recognized by Rack (ModSoft) Possible Causes • Module not correctly installed. • Module runtime files not correctly installed. Corrective Action 1. Reinstall the module in the rack. See chapter 2, “Installation and Wiring.” 2. Check the I/O map screen in ModSoft to see if the problem still exists. 3.
Quantum Series 140 EHC 204 00sc Index Numerics 24V gate enable 3-18 3X rreegister isterss 1-11, 3-1 4X rreegister isterss 3-1, 3-13 4X+2 rreegister 3-20 4X+3 rreegister 3-21 4X+4 rreegister 3-22 4X+6 rreegister 3-20 4X+7 rreegister 3-21 4X+8 rreegister 3-22 A accuracy overall 2 acti v hannel 3-15 activate cchannel acti vating de vices 5-1 activ devices acti ve LED 1-6 activ ad dr essing 3-1 addr dressing status word 1-11 applications 1-1 B backplane 1-10 backplane interface 1-7 bank number 3-16 bidir e
Counter / Flow Meter Input Module errors 1-11, 5-12 verification 4-4 conf igur ation er te 3-26 configur igura errror sta state conf igur ation pr ograms 3-1, 3-2 configur igura pro conf igur ation rreegister configur igura isterss 3-1 conf igur ation w or d1 configur igura wor ord contamination 2-5 contr ol w or d ena ble 3-15 control wor ord enab contr oller 1-1 controller count dir ection 3-9, 3-18 direction count dir ection sta te 3-24 direction state count size 3-9 count size state 3-24 counter enable
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc critical 5-9 data definition 5-10 extended error information field 5-11 general common hardware 5-11 hardware-specific 5-12 module 5-9 module error field 5-10 noncritical 5-9 reporting 5-3 ESD 2-3 extended er or ma tion ffield ield 5-11 errror inf infor orma mation F fault LED 1-6 blink codes 1-6 field wir ing 2-9 wiring filter 15 kHz 3-8 30 kHz 3-8 filter fr equenc y2 frequenc equency filter ilterss 1-2 flags counter limit 3-19 counter maximum 3-19 count
Counter / Flow Meter Input Module K K or M scale factor state 3-25 K scale factor 3-21 L ladder logic 4-1 least signif icant w or d2 significant wor ord LEDs 1-5 location of module 2-5 LSW 3-15, 2 M M scale factor 3-21 maintenance 5-1 safety considerations 5-1 ModSoft 3-2, 3-10 module 1-1 addressing 3-1 environment 2-7 errors 5-9 features 1-4 hardware features 1-4 inserting in rack 2-8 inspection 5-5 installing 2-7 location 2-5 operation 1-7 overview 1-1 removing 2-8 specifications A-1 wiring 2-9 wiring
Quantum Series 140 EHC 204 00sc O operation module 1-7 system 1-11 output rreegister isterss 3-1 P par ameter rreegister parameter isterss 3-1 ph ysical specif ica tions A-1 physical specifica ications PLC 1-1 po wer 1-1 pow removing during installation 2-4 po wer -up dia gnostics 5-3 pow er-up diagnostics pr eset 3-17 preset pr ogram alter ation 5-2 pro altera pr ogram EEPR OM 3-17 pro EEPROM pr ogramming 4-1 pro Pr oW or ks 3-2 ProW oWor orks Q quadr atur ation 3-7 quadra turee 1X oper opera quadr atu
Counter / Flow Meter Input Module remo ving module fr om rrac ac k 2-8 emoving from ack reset ffla la gs lags 3-18 roll oov ver 3-9 roll under 3-9 runtime ffiles iles 1-1, 3-2 S saf ety cir cuits 5-2 safety circuits safety standards 2-1 CUL 2-1 UL 2-1 sampling time 2 scaling/data mode 3-15 specif ica tions A-1 specifica ications electrical A-3 environmental A-2 physical A-1 standards compliance A-5 standards compliance A-5 sta tus rreegister status isterss 3-1 sta tus w or d 1-11 status wor ord stop on li
Quantum Series 140 EHC 204 00sc unidir ectional oper ation 3-7 unidirectional opera V ver ifying cchannel hannel conf igur ation 4-4 erifying configur igura W wiring 2-9, 2-11 documents 2-3 Z zoom rreegister isterss 3-1 setup ModSoft 3-10 setup using Concept 3-12 72 140 EHC 208 00sc
Counter / Flow Meter Input Module Glossary The following terms and abbreviations are used throughout this manual. A/D converter The analog-to-digital converter used in the module. The converter produces a digital value with a magnitude that is proportional to the magnitude of an analog input signal. attenuation Reduction in the magnitude of a signal as it passes through a system.
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc input data scaling Data scaling that depends on the data format selected for a channel configuration word. LSW Least significant word. module update time The time required for the module to sample and convert the input signals of all enabled input channels and make the resulting data values available to the processor. MSW Most significant word. multiplexer A switching system that allows several input signals to share a common A/D converter.
Counter / Flow Meter Input Module 75
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc AAppendix Specifications This appendix lists the specifications for the Quantum counter module. Specification Value Data Registers 8 - 3X registers 10 - 4X registers 8 - zoom (parameter) registers LED Indicators: 1 Green LED, Module Status The module status LED indicates the status of the power-up self-test. The LED is on when the module is ready. Any self-test error is indicated with a blink code.
Counter / Flow Meter Input Module Electrical Fast Transient IEC 801-4 Radiated Emissions CISPR 11 Class A Surge Impulse IEC 801-5 Conducted Immunity IEC 801-6 Fast Surge Immunity EN61000-4-5 Voltage Dropouts (Variation and Dips) EN61000-4-11 Electrical Specifications Specification Configuration enable control lines Input Modes Voltage Range: VIL1 VIH Vmax CE Current Range Input Impedance Counter Speed: DC Inputs 5V, 12V, 24V, AC Input Frequency: DC Inputs AC Inputs Counter Enable Input: Value 8 channels
Quantum Series 140 EHC 204 00sc Input Protection Power Requirements: Internal Rack +5V 140 EHC 208 00sc Max. input voltage ±75VDC continuous, 106VAC peak Max. input current less than or equal to 6 mA at 75VDC Less than 650 mA - 8 channel Less than 470 mA - 4 channel Standards Compliance The following certifications will be obtained: • UL 508. • CUL and Class 1, Division II (CSA equivalent). • CE compliance with EN 61010-1 and EN 61131-2, EN50081-2, EN50082-2.
Counter / Flow Meter Input Module 79
Quantum Series 80 140 EHC 204 00sc 140 EHC 208 00sc
Spectrum Controls Support If you need technical assistance, please review the information in chapter 5, “Maintenance and Diagnostics.” If you still have questions, call your local distributor of Spectrum Controls products. Note that your module contains electronic components that are susceptible to damage from electrostatic discharge (ESD). An electrostatic charge can accumulate on the surface of ordinary plastic or cushioning material.
The Schneider Alliances logo is a trademark of Schneider Electric. © 2001 Spectrum Controls, Inc. All rights reserved. Printed in U.S.A. Specifications subject to change without notice. Owners Guide 030018501 Rev. A Corporate Headquarters: P.O. Box 5533 Bellevue, Washington 98006 Tel: (425) 746-948 Fax: (425) 641-9473 Northeastern U.S.A. Sales Office 48945 Van Dyke, 4B Utica, Michigan 48317 Tel: (586) 731-2397 Fax: (586) 731-2715 Southeastern U.S.A. Sales Office 5300 Regency Lake Ct.