User guide

Spectrex Inc. - SafEye
TM
300 Gas Detector Manual TM 794100, Rev. D, May 2004
2.1 Terminal Wiring
Each detector and source unit has a separate EExe terminal box directly
attached/assembled to it and prewired to the terminal strip in the EExe box (Item
4). There are two possible wiring options please follow the wiring scheme
below which is appropriate to that ordered:
The terminal block is labeled 1 to 6 (See Fig. No.25)
The following describes the function of each electrical terminal of the detector:
RS-485 & 4-20mA Version
Option A (See Fig. No. 26)
Alarm & Fault Relays Version
Option B (See Fig. No. 27)
Power Supply
(Terminal Numbers 1, 2):
Input power - Terminal No. 1.
RETURN - Terminal No. 2.
Power Supply
(Terminal Numbers 1, 2):
Input power - Terminal No. 1.
RETURN - Terminal No. 2.
RS-485 as specified in appendix C.
(Terminal Numbers 3, 4):
Terminal No. 3 - positive (+) lead.
Terminal No. 4 - negative (-) lead.
Alarm Relay (Terminal Numbers 3, 4):
The Alarm output is a NO. SPST
contact at Terminal Numbers 3 and 4.
The contacts are closed at Alarm
Mode.
4-20mA Output (Terminal Numbers 5,
6): as specified in paragraph 5.e
Terminal No. 5 - output Terminal.
Terminal No. 6 - input Terminal.
(see appendix B for more details)
Fault Relay (Terminal Numbers 5, 6):
The Fault output is N.C. SPST contact
at Terminal Numbers 5 and 6. The
contacts are open at Fault condition.
Figure 26: OPTION A
Detector Assembly - Wiring Diagram
Figure 27: OPTION B
Detector Assembly - Wiring Diagram