Manual

Spectrex Inc. - SafEye
TM
200 Gas Detector Manual TM 792100, Rev. D, May 2004
3.9 System Setup
3.9.1 Detector Setting
The detector consists of the following DIPswitches, which enable the user to
adapt the detector operation to specific application:
SW1 Function Selection Switch. Contains. 8 DIPswitches. Used for Calibration
of different gas selection, response time control and Relays response
configuration (see table 7)
SW2 Address Selection Switch. Contains 8 DIPswitches. Used for Detector’s
address setting and 4-20mA output configuration setting (see table 10)
SW3 Alarm Options Selection Switch. Contains 4 DIPswitches. Used for
Detector’s Alarm Latching configuration and 4-20mA level reading
configuration (see table 11)
Function Selection Switch:
Table 7 describes SW1 DIPswitches position and the required function for setting
the detector according to the necessary configuration
Table 7. SW1 DIPswitches Configuration
Switch
No.
Off position On position Default
setting
1 Detection speed control bit
0 at “0” (see note 1 below)
Detection speed control bit 0
at “1” (see note 1 below)
on
2 Detection speed control bit
1 at “0” (see note 1 below)
Detection speed control bit 1
at “1” (see note 1 below)
off
3 Gas type control bit 0 at “0”
(see note 2 below)
Gas type control bit 0 at “1”
(see note 2 below)
on
4 Gas type control bit 1 at “0”
(see note 2 below)
Gas type control bit 1 at “1”
(see note 2 below)
off
5 Full scale sensitivity is 0-5
LEL.m
Full scale sensitivity is 0-2
LEL.m
off
6 Zero calibration is
performed according to
background
Gas level detection
performed without
background Zero calibration
off
7 Accessory Relay is
activated at Warning level
Accessory Relay is activated
at Alarm level (with the
Alarm Relay)
off
8 Accessory Relay is
activated according to SW1-
7 position
Accessory Relay is Activated
at Power on continuously
(used as End of Line)
off