Manual

Spectrex Inc. - SafEye
TM
200 Gas Detector Manual TM 792100, Rev. D, May 2004
5
2.4 Product Marking
The SafEye 200 Series open path gas Detector and source unit are certified to:
1. ATEX Ex II 2 G per SIRA 00 ATEX 1161 & 1165
EExd IIB +H
2
T6 and EExde IIB +H
2
T6 Amb. Temp. -40°C to +55°C
2. UL E209870 Class I, Group C and D
2.5 Models and Types
This manual includes information for SafEye Series 200 models. Table 1
identifies the detector model options in reference to the required gas type and
detection range.
Table 1: Model Selection Guideline for SafEye Series 200 IR Type
Distance Model
Ft. m.
Detector* Flash
Source*
Option
for Duct
Mount
Option for
St.St
Enclosure
202 9.8-39.4 3-12 OP-IF100x OPS-FI0x Yes Yes
203 33-131 10-40 OP-IF100x OPS-FI1x No Yes
204 49-197 15-60 OP-IF100x OPS-FI2x No Yes
226 98-295 30-90 OP-IF100x OPS-FI3x No Yes
227 164-459 50-140 OP-IF101x OPS-FI3x No Yes
* Notes
For standard installation add “S” suffix. For duct installation add “D” suffix. For St.
St. version add “St” suffix after the “D” or the “S” suffix.