Instruction Manual
Technical Specifications 43
A Specifications
➣ In this appendix…
Technical Specifications
page 43
Electrical Specifications
page 44
Outputs
page 44
Approvals
page 46
Mechanical Specifications
page 46
Environmental Specifications
page 47
A.1 Technical Specifications
Spectral Response
Multi IR Bands
Detection Range
(at highest Sensitivity
Setting for 1ft
2
(0.1m
2
) pan
fire)
Fuel
ft. / m
Fuel
ft. / m
n-Heptane
215 / 65
Kerosene
150 / 45
Gasoline
215 / 65
Ethanol 95%
135 / 40
Diesel Fuel
150 / 45
Methanol
115 / 35
JP5
150 / 45
IPA (Isopropyl
Alcohol)
135 / 40
Methane*
100 / 30
Polypropylene
Pellets
16 / 5
LPG*
100 / 30
Ammonia*
40 / 12
Hydrogen*
100 / 30
Silane*
16 / 5
Office Paper
33 / 10
* 20" (0.5m) high, 8" (0.2m) width plume fire
Response Time
Typically 5 seconds
Adjustable Time Delay
Up to 30 seconds
Sensitivity Ranges
2 ranges for 1 ft
2
(0.1m
2
) n-heptane pan fire from 50 ft. (15m)
to 215 ft. (65m)
Fields of View
Gasoline: Horizontal 67, Vertical 70
Hydrogen: Horizontal 80, Vertical 80
Built-In-Test (BIT)
Automatic (and Manual)