User Manual

Technical Specifications 43
A Specifications
In this appendix…
Technical Specifications
page 43
Electrical Specifications
page 44
Outputs
page 44
Approvals
page 46
Mechanical Specifications
page 47
Environmental Specifications
page 47
A.1 Technical Specifications
Spectral Response
Three IR Bands
Detection Range
(at highest Sensitivity
Setting for 1ft
2
(0.1m
2
) pan
fire)
Fuel
ft. / m
Fuel
ft. / m
n-Heptane
215 / 65
Kerosene
150 / 45
Gasoline
215 / 65
Ethanol 95%
135 / 40
Diesel Fuel
150 / 45
Methanol
115 / 35
JP5
150 / 45
IPA (Isopropyl
Alcohol)
135 / 40
Methane*
100 / 30
Polypropylene
Pellets
16 / 5
LPG*
100 / 30
Office Paper
33 / 10
* 20" (0.5m) high, 8" (0.2m) width plume fire
Response Time
Typically 5 seconds
Adjustable Time Delay
Up to 30 seconds
Sensitivity Ranges
4 Sensitive ranges for 1 ft
2
(0.1m
2
) n-heptane pan fire from
50 ft. (15m) to 215 ft. (65m)
Fields of View
Horizontal 100, Vertical 95
Built-In-Test (BIT)
Automatic (and Manual)