7.2 Reset
Note: This is available only when the optional latching alarm has been
selected.
To RESET a detector when in its ALARM state, disconnect power.
7.3 Functional Testing
The detector can be tested for proper functioning using the Fire Simulator
Model 20/20-310.
7.3.1 Testing with Fire Simulator Model 20/20-310
Refer to Long Range IR3 Fire Simulator on page 45.
This test simulates an exposure of the detector to a real fire condition. The
detector is exposed to radiation at the required detection level. As a result,
the detector must generate a Fire Alarm signal.
Important Note: If the detector is exposed to a fire simulator,
the Alarm Relay and 0-20 mA will be activated during the
simulation. Therefore, automatic extinguishing systems or any
external devices, which may be activated during this process,
must be disconnected.
To test with Fire Simulator Model 20/20-310
1 (If the detector is ON, skip this step.)
Apply power to the system and wait up to 60 seconds for the detector to
turn to the normal state.
The 1 Hz LED flashes green.
2 Aim the Spectrex Fire Simulator Model 20/20-310 at the target point of
the detector (see Figure 12), in such a way that the radiation emitted by
it is facing directly towards the detector. (See Long Range IR3 Fire
Simulator on page 45.)
3 Press the operation button once. After few seconds, the following occurs:
The LED lights up red constantly for a few seconds.
The 0-20 mA output turns to 20 mA for a few seconds and then
returns to 4 mA.
The Alarm Relay also turns on.
This completes the installation procedure. The detector and system are now
ready for operation.