Manual

Spectrex Inc. - SharpEye
TM
Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011
22
5.3 Environmental Specifications
High Temperature
Design to meet MIL-STD-810C, method 501.1 procedure II
Operating temperature: +160 °F (+70 °C)
Storage temperature: +185 °F (+85 °C)
Low Temperature
Design to meet MIL-STD-810C, method 502.1, procedure I
Operating temperature:
-40 °F (-40 °C)
Storage temperature: -65 °F (-55 °C)
Humidity
Design to meet MIL-STD-810C, method 507.1, procedure IV
Relative humidity of up to 95% for the operational temperature range.
Salt Fog
Design to meet MIL-STD-810C, method 509.1, procedure I
Exposure to a 5% Salt Solution Fog for 48 hours.
Dust
Design to meet MIL-STD-810C, method 510.1, procedure I
Exposure to a dust concentration of 0.3 frames/cubic ft. at a velocity of
1750 fpm, for 12 hours.
Vibration
Design to meet MIL-STD-810C, method 514.2, procedure VIII
Vibration at an acceleration of 1.1g within the frequency range of 5-30 Hz,
and an acceleration of 3g within the frequency range of 30-500 Hz.
Mechanical Shock
Design to meet MIL-STD-810C, method 516.2, procedure I
Mechanical Shock of 30g half-sin wave, for 11 msec.
Electromagnetic Compatibility (EMC):
This product is in conformance with EMC directive 89/336/EC.
Radiated Emission EN61000-6-3
Conducted Emission EN61000-6-3
Radiated Immunity EN61000-4-3
Conducted Immunity EN61000-4-6
ESD EN61000-4-2
Burst EN61000-4-4
Surge EN61000-4-5